Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification and abbreviated (NY 460 and NY 485) surveys conducted 9/23/2024-9/26/2024, the facility did not ensure residents who were unable to carry out activities of daily living received the necessary services to maintain good nutrition, grooming, and personal and oral hygiene for 2 of 7 residents (Resident #15 and #43) reviewed. Specifically, Resident #43 was not assisted with removing unwanted facial hair, and Resident #15 had unkept hair and unclean and untrimmed fingernails. Findings include: The facility policy, Activities of Daily Living Care and Support, revised 3/13/2024, documented activities of daily living care and support would be provided for residents who were unable to carry out activities of daily living independently, in accordance with the resident's assessed needs, personal preferences, and individualized plan of care, that included but was not limited to supervision and assistance with: hygiene, mobility, elimination, dining, and communication. Nail care would be provided as needed for residents and facial hair would be groomed as per residents' preference and/or assessed needs. 1) Resident #43 had [DIAGNOSES REDACTED]. The 7/8/2024 Minimum Data Set assessment documented the resident was cognitively intact, was dependent with toileting hygiene, shower/bathing, and lower body dressing, required setup or clean-up assistance with eating and oral hygiene, and did not refuse care. The comprehensive care plan initiated 6/14/2024 documented the resident required assistance with self-care and mobility related to impaired balance and limited mobility. Interventions included partial assistance with personal hygiene and substantial assistance with showering/bathing. The 9/2024 certified nurse aide care record documented the resident received personal care during the day and evening shift on 9/23/2024-9/25/2024. Resident #43 was observed at the following times: - on 9/23/2024 at 12:10 PM, in their room seated in their wheelchair. They had thick brown hair covering their upper lip and long gray/white hair under their chin. The resident stated they did not want facial hair. - on 9/24/2024 at 9:10 AM, in their room seated in their wheelchair. They had thick brown hair covering their upper lip and long gray/white hair covering their chin. - on 9/25/2024 at 9:38 AM, in their room seated in their wheelchair. They had thick brown hair covering their upper lip and long gray/white hair covering their chin. The resident stated they hoped staff had time to shave them because they did not want facial hair when they attended the Fall Festival activity. During an interview on 9/25/2024 at 1:10 PM, Certified Nurse Aide #34 stated they looked at the resident's care instructions to know how to properly care for each resident. Personal hygiene consisted of cleaning the resident head to toe, nail care, oral care, and shaving. They stated after they completed all personal hygiene, they documented the care was completed. If a resident refused, they would document the refusal and notify the nurse so they could reapproach the resident. They were familiar with Resident #43, they did not refuse care, and they assisted with their care that day. The stated they shaved the resident because they had a lot of facial hair, and they thought another certified nurse aide should have done it earlier that week when they were not working. It was important for the certified nurse aides to offer shaving whenever facial hair was present to maintain resident dignity. During an interview on 9/25/2024 at 3:42 PM, Licensed Practical Nurse #14 stated staff looked at a resident's care plan or care instructions to tell them how to properly care for the resident. Personal hygiene was completed each shift and consisted of washing a resident's face and body, nail care, hair care, shaving, and oral care. If a resident refused care, the certified nurse aides would notify the nurse so they could reapproach the resident. They had not been notified of any refusals by Resident #43. They stated it was important for the certified nurse aides to shave Resident #43 for their self-image and to maintain their dignity. During an interview on 9/26/2024 at 9:26 AM, Certified Nurse Aide #36 stated residents received showers twice a week and they would shave resident's when they were in the shower. They gave Resident #43 a shower on 9/23/2024 and they could not recall if they shaved the resident, but they normally would during a shower. Resident #43 never refused care but if they had, they would have notified the nurse. They stated it was important to shave Resident #43 whenever they had facial hair to maintain their dignity. During an interview on 9/26/2024 at 10:25 AM, the Assistant Director of Nursing stated personal hygiene consisted of oral care, bathing, dressing, nail care, and shaving. They stated personal hygiene should be offered and completed daily for each resident. The electronic documentation system only asked certified nurse aides if all care was completed, and they would answer yes or no. If a resident refused care, they should notify the nurse so they could reapproach the resident. It was important for the certified nurse aides to offer shaving whenever Resident #43 had facial hair to boost their self-esteem and to maintain their dignity. 2) Resident #15 had [DIAGNOSES REDACTED]. The 6/30/2024 Minimum Data Set assessment documented the resident required modified independence for daily decision making, did not refuse care, and required maximum assistance for hygiene care. The comprehensive care plan initiated 3/4/2021 documented the resident required assistance with activities of daily living and was at risk for impaired skin integrity. Interventions included keep fingernails short to prevent scratches, showers on Tuesday and Friday evenings, and substantial assistance of one for personal hygiene tasks. The (MONTH) 2024 Documentation Survey Report documented the resident received a shower on 9/24/2024 (Tuesday) by Certified Nurse Aide #25. There was no documentation the resident received a shower on 9/20/2024 (Friday). Resident #15 was observed in their room with long, jagged nails with brown debris and unkempt, matted hair on 9/23/2024 at 11:14 AM, 9/24/2024 at 8:34 AM, and 9/25/2024 at 9:08 AM. The resident stated their nails were too long, their hair had not been washed in 2 weeks, and they did not receive a shower on 9/24/2024. During an interview on 9/25/2024 at 11:13 AM, Certified Nurse Aide #25 stated showers were given twice a week and were documented in the bathing task. Bed baths were given in place of a shower if a resident requested. Hair washing was included in both showers and bed baths. If the shower task documentation stated yes then it meant a shower was given which included hair washing. Nail care was provided whenever needed and could be performed by aides if the resident was not a diabetic. Hair combing was completed every day. Any refusal of care was reported to the nurse. They gave Resident #15 a bed bath last evening at the resident's request but did not wash their hair because they received a bed bath and not a shower. They did not report to the nurse that hair washing was not completed. If residents did not receive their showers or have their hair washed it could cause that resident to feel uncomfortable, moody, or grumpy. Nail care was important because dirty nails could spread bacteria which could cause illness. During an interview on 9/25/2024 at 1:00 PM, Licensed Practical Nurse #6 stated residents received showers twice a week that included hair washing and nail care. Certified nurse aides should provide nail care anytime there was a need unless the resident was a brittle diabetic. Daily morning care should include hair combing. Any refusals of showers, nail care, or hair care should be reported to and documented by the nurse. Resident #15 usually received a shower or a bed bath. They had not noticed the resident's nails, but they should be clean and not jagged. No one had reported to them that Resident #15 refused any care. During an interview on 9/26/2024 at 10:08 AM, Licensed Practical Nurse Manager #22 stated they expected showers were given according to the shower schedule and included nail care and hair washing. If a bed bath was given, hair should still be washed. Nail care was done anytime they were long, jagged or debris was present, and hair combing was provided daily. Resident #15 required substantial assistance with hygiene care. If a shower was signed for by the aide, then it implied that hair was washed as well. During an interview on 9/26/2024 at 10:25 AM, the Assistant Director of Nursing stated showers were provided twice a week and were documented by the certified nurse aides in the electronic record. Personal care included nail care and should be offered daily. It was important to clean and clip nails whenever they were dirty or long to prevent cuts and infections. If nail care or hair care was needed, it should not wait until shower days to be provided. Residents should not have greasy hair and should be offered to have hair washed even if it was not their shower day. Not providing good hygiene could be a dignity and self-esteem issue. 10NYCRR 415.12(a)(3) | Plan of Correction: Approved October 15, 2024 Resident #15 was showered, hair washed, and fingernails cleaned, trimmed and filed smooth. Resident #43 was assisted with removing unwanted facial hair. All dependent residents were observed for and if needed addressed for unwanted facial hair, unkempt hair, and unclean and untrimmed fingernails. All concerns were addressed immediately. All nursing staff (CNA/LPN/RN) were re-educated on ADL care for dependent residents per policy with a focus on unwanted facial hair, unkempt hair, and unclean and untrimmed fingernails. DON or designee will randomly audit 5 dependent residents for cleanliness, clean, combed hair, clean trimmed fingernails, and unwanted facial hair weekly for 4 weeks, then monthly for 3 months. Results will be brought to the QAPI committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI committee is achieved. Responsible Party: Director of Nursing |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure that residents who required [MEDICAL TREATMENT] services (filtration of blood when the kidneys do not work) received such services consistent with professional standards of practice for 1 of 1 resident (Resident #17) reviewed. Specifically, Resident #17 received [MEDICAL TREATMENT] treatments at a community-based [MEDICAL TREATMENT] center and did not have on-going assessments and oversight before and after [MEDICAL TREATMENT] treatments. Additionally, staff documented the resident had an arteriovenous fistula (surgical connection between an artery and a vein often used for [MEDICAL TREATMENT] access) which the resident did not have. Findings include: The facility policy, [MEDICAL TREATMENT] Access Care, revised 5/2019, documented the central catheter (a tube inserted into a large, central vein) site was kept clean and dry at all times and bathing and showering were not permitted with this device. Catheter lumens (outside ends of the catheter) were capped and clamped when not in use. The general medical nurse documented in the resident's medical record every shift the location of the catheter, condition of the dressing, if [MEDICAL TREATMENT] was done during the shift, and any report from [MEDICAL TREATMENT] nurse post-[MEDICAL TREATMENT] and observations post [MEDICAL TREATMENT]. The facility policy, [MEDICAL TREATMENT] Management, revised 5/2019, documented residents that received [MEDICAL TREATMENT] treatments were assessed and monitored and ensured quality of life and well-being. The access site was observed for function and signs and symptoms of infection. Orders were obtained for monitoring of the site and interventions as appropriate. Permacaths (a central catheter used for long-term access) were observed for bleeding and placement. The nurse would evaluate the resident post [MEDICAL TREATMENT] for access site condition and document in the nurse's notes. Resident #17 had [DIAGNOSES REDACTED]. The 7/19/2024 Minimum Data Set assessment documented the resident had moderately impaired cognition, did not reject care, had end stage [MEDICAL CONDITION], and required [MEDICAL TREATMENT] treatments. The Comprehensive Care Plan initiated 5/22/2024 documented the resident needed [MEDICAL TREATMENT] related to end stage [MEDICAL CONDITION]. Interventions included the check the access site dressing daily; change dressing only if ordered by the physician; document condition and complications; monitor for signs of infection such as redness, swelling, warmth, or drainage and document; and monitor the Permacath to the right upper chest for bleeding and placement. The resident received [MEDICAL TREATMENT] on Monday, Wednesday, and Friday with a 6:00 AM pick up time and a 7:00 AM chair time. The 8/12/2024 physician order [REDACTED]. If bleeding was noted, pressure was to be applied, and the physician was to be notified. If dislodged, pressure was applied and 911 was to be called. The order did not specify the location of the Permacath. The [MEDICAL TREATMENT] communication book documented the resident attended [MEDICAL TREATMENT] on 9/2/2024, 9/4/2024, 9/6/2024, 9/9/2024, 9/11/2024, 9/13/2024, 9/16/2024, 9/18/2024, 9/20/2024, 9/23/2024 and 9/25/2024. There was no documented evidence of pre-[MEDICAL TREATMENT] evaluations on 9/2/2024, 9/13/2024, 9/18/2024, 9/20/2024, and 9/23/2024. There was no documented evidence of post-[MEDICAL TREATMENT] evaluations on 9/4/2024, 9/6/2024, 9/13/2024, and 9/20/2024. During an observation and interview on 9/23/2024 at 12:21 PM, Resident #17 stated they attended [MEDICAL TREATMENT] on Monday, Wednesday, and Friday at a community-based [MEDICAL TREATMENT] center and they had just gotten back. The resident had a right chest dual lumen Permacath for [MEDICAL TREATMENT] covered with a white dressing that was clean, dry, and intact. They did not recall if the facility obtained vital signs or weights before or after [MEDICAL TREATMENT] treatments. There was a binder that went with them back and forth from [MEDICAL TREATMENT]. The 9/23/2024 Licensed Practical Nurse #28 post [MEDICAL TREATMENT] evaluation documented the resident had a Permacath and their arteriovenous fistula bruit (swooshing sound that indicates the fistula is working) was audible, and thrill (a vibration that can be felt when placing fingers over the arteriovenous fistula indicating blood flow) was present. No site changes of the arteriovenous fistula. There was no documented evidence in the resident's medical record of an arteriovenous fistula. The 9/25/2024 Licensed Practical Nurse #14 post [MEDICAL TREATMENT] evaluation documented the resident had a Permacath and the arteriovenous bruit was audible, and thrill was present. No site changes of the arteriovenous fistula. During an interview on 9/25/2024 at 1:35 PM, Licensed Practical Nurse #14 stated pre and post [MEDICAL TREATMENT] assessments were documented electronically. Resident #17 had a Permacath, but they did not remember where their access site was located. They had completed the resident's post [MEDICAL TREATMENT] assessment today around 11:30 AM when the resident returned from [MEDICAL TREATMENT]. They looked at the access site with that assessment. They checked the electronic medical record and confirmed they completed the post [MEDICAL TREATMENT] assessment at 11:37 AM but was not sure where the access site was located. It was important the site was monitored because the resident could bleed out. During an interview on 9/25/2024 at 3:29 PM, Licensed Practical Nurse #28 stated Resident #17 had a Permacath to their left chest for [MEDICAL TREATMENT]. The dressing was supposed to be clean, dry, intact and without signs of infection. They were not sure if the site should be monitored for anything else. The pre and post [MEDICAL TREATMENT] assessments were documented and if they were not documented, they were not done. During a follow up interview on 9/26/2024 at 9:46 AM, Licensed Practical Nurse #28 stated the resident had a right chest Permacath only and did not have an arteriovenous fistula. They showed the surveyor the electronic charting of the post [MEDICAL TREATMENT] note. They documented on an arteriovenous fistula because not applicable was not an option. It was not appropriate to document on an arteriovenous fistula because Resident #17 did not have one. During an interview on 9/26/2024 at 10:35 AM, Licensed Practical Nurse Unit Manager #22 stated pre and post [MEDICAL TREATMENT] assessments were completed and contained information about the site appearance and type of access site. An arteriovenous fistula should not be documented if the resident did not have that type of access site. It was important the site was monitored for bleeding and signs of infection. It was also monitored every shift and documented in the Treatment Administration Record and if it was documented, it meant the nurse looked at the site. Resident #17 received [MEDICAL TREATMENT] and the site should be monitored. During an interview on 9/26/2024 at 11:18 AM, the Assistant Director of Nursing stated the pre-[MEDICAL TREATMENT] assessment documented either a Permacath access site or an arteriovenous fistula. The nursing staff checked the [MEDICAL TREATMENT] site for bleeding, if the Permacath was intact, and not pulled out. If it was not documented, it was not done. The site was monitored every shift for displacement, bleeding, and signs of infection. If the site was monitored staff should know where the site was located. Resident #17 received [MEDICAL TREATMENT] and had a right chest Permacath. They checked the resident's electronic medical record and the pre and post [MEDICAL TREATMENT] assessments were not being consistently done but should have been. It was especially important the site was monitored after [MEDICAL TREATMENT] because there could be a medical emergency. It was important that any changes to the site appearance or the resident's vital signs were communicated to [MEDICAL TREATMENT] and without the appropriate assessments, changes were not monitored. 10NYCRR 415.12(k) | Plan of Correction: Approved October 15, 2024 **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Documentation for Resident #17 cannot be completed retroactively, however moving forward, all pre and post [MEDICAL TREATMENT] notes will be completed prior to and following each [MEDICAL TREATMENT] treatment. LPN #14 was educated on evaluation of [MEDICAL TREATMENT] access and the difference between an AV Fistula and a Permacath. LPN #14 was also educated on timely and appropriate completion of pre/post [MEDICAL TREATMENT] note. All medical records for residents receiving [MEDICAL TREATMENT] were reviewed for appropriate completion of pre and post [MEDICAL TREATMENT] assessments. All nurses (LPN/RN) were educated on evaluation of [MEDICAL TREATMENT] site and the difference between AV Fistula and Permacath. All nurses (LPN/RN) were also educated on timely and appropriate completion of pre/post [MEDICAL TREATMENT] note. DON or designee will audit medical records of all residents receiving [MEDICAL TREATMENT] to ensure appropriate completion of pre/post [MEDICAL TREATMENT] note and accuracy of documented [MEDICAL TREATMENT] access weekly for 4 weeks. Then monthly for 3 months. Results will be brought to the QAPI Committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI Committee is achieved. Responsible Party: Director of Nursing |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interview during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure the discharge needs of each resident were identified and resulted in the development of a discharge plan for 1 of 1 resident (Resident #54) reviewed. Specifically, Resident #54 expressed the intention to be discharged to an assisted living facility and was not assisted with discharge planning or updated on the status of their discharge plan. Findings include: The facility policy, Discharge-Planning, revised 12/2019, documented the discharge planning process ensured residents had a discharge plan of continuing care that met their post-discharge needs and a goal of a safe and successful transition to the community, a lower level of care, or alternate healthcare facility. The Social Worker was responsible for the duties of Discharge Coordinator. The Discharge Coordinator developed a discharge plan that began on admission for each resident, initiated all necessary referral for post discharge care and needs, and documented the steps taken for discharge planning in the resident's medical record. Resident #54 was admitted to the facility with [DIAGNOSES REDACTED]. The 7/8/2024 Minimum Data Set assessment documented the resident was cognitively intact, had no behavioral symptoms, required supervision or set-up assistance with most activities of daily living, was independent with transfers and ambulation, and active discharge planning was not occurring. The comprehensive care plan initiated 7/28/2024 documented the resident's placement was long-term care and the resident did not wish to be asked about returning to the community on all assessments. Interventions included participation in social/ recreational activities to promote well-being and support and encouragement were provided. The 4/26/2024 Physical Therapist #12 discharge progress note documented the resident had reached their goals upon discharge. The discharge recommendations were assistance with instrumental activities of daily living (preparing meals, managing medications, cleaning, getting around with transportation and managing money). The 4/26/2024 Occupational Therapist #13 discharge progress note documented the resident had reached maximum potential with skilled services and made consistent progress with skilled interventions. The 6/4/2024 Director of Social Work Social Services Assessment documented the resident was responsible for themself, and their goal was to be discharged to another facility/ institution. The resident was readmitted to the facility, and they were to remain long-term care and work on their well-being. There was no documented evidence the Director of Social Work discussed discharge goals and the need for long-term placement with the resident. The resident's Notice of Medicare Non-Coverage documented Medicare covered Skilled Nursing Facility Services would end on 6/20/2024. The resident signed the notice on 6/18/2024. The 8/5/2024 Psychiatric Mental Health Nurse Practitioner #10 progress note documented the resident reported they were waiting for assisted living placement. The 8/6/2024 Physician #9 progress note documented the resident was at their treatment and care plan goals and was to be discharged to assisted living if possible. The 8/24/2024 Psychiatric Mental Health Nurse Practitioner #10 progress note documented the resident reported that they continued to wait for assisted living placement. There was no documented evidence the possibility of discharge to an assisted living facility was discussed with the resident or if referrals were made. During an interview on 9/23/2024 at 10:08 AM, the resident stated they were trying to find somewhere else to live. During an interview on 9/25/2024 at 8:58 AM, the resident stated they went out with family yesterday. They went shopping, out to eat, and got a new cellular phone. Their social worker was supposed to be helping them get to an assisted living facility for the past 4-6 months. They asked their social worker every day, and their social worker told them they had not heard anything. When they talked to their social worker a couple of days ago, the social worker said they were going to call some facilities. They did not know if they had made any calls yet or to what facilities. They wanted to move closer to where they lived prior to coming to the facility. During an interview on 9/25/2024 at 12:59 PM, Certified Nurse Aide #15 stated the Director of Social Work was responsible for and assisted residents with discharge planning. Resident #54 did not need any assistance from the certified nurse aides. The resident bathed, brushed their teeth, washed their face, and dressed themselves independently. They thought the resident could probably live in an assisted living facility. During an interview on 9/25/2024 at 1:29 PM, Licensed Practical Nurse #14 stated the resident was independent with activities of daily living. It was important the resident went to a lower level of care to facilitate independence and it would be beneficial for mood and lifestyle. The resident spent their days either in their room or the dining room and if they were at an assisted living facility, they could go for a walk or do many different things. The Director of Social Work was responsible for assisting residents with discharges. During an interview on 9/25/2024 at 1:54 PM, the Director of Social Work stated the discharge process started on their first visit within 3 days of admission. They were the only social worker for the facility. Prior to discharge the resident had to be cleared by the physician, medical staff, and therapy. If a resident was appropriate to be discharged to assisted living, they sent out referral packets via facsimile. They then waited for call backs and followed up periodically if they had not heard anything back. When Resident #54 was discharged from therapy, discharge to assisted living was discussed. The resident wanted to go somewhere close to where they lived before, but they were not familiar with the facilities in that area. They stated the resident would do great in an assisted living setting. For the past 2 weeks the resident came to their office every morning and asked about moving to an assisted living facility and they told the resident they had not forgotten about them and that the process took time. It was important that progress of the process was communicated with the resident. They could not remember how long it was since the resident first approached them about moving to an assisted living facility but at that time there were long wait lists. They had not yet sent out any referral packets for Resident #54. The resident's family came to them today and asked about a transfer to another facility as well. 10NYCRR 415.11(d)(3) | Plan of Correction: Approved October 15, 2024 Director of Social Work made referrals to Assisted Living Facilities as requested by resident #54.Discharge planning efforts were documented in the residents medical record and the resident was updated regarding current status of discharge plan. All residents have the possibility to be effected. A full-house audit will be completed to identify any resident (and/or resident representative when applicable) requesting discharge planning, and to ensure that discharge planning efforts have been made and that the current status of discharge plan is documented in the EHR and communicated to the resident (and/or resident representative when applicable). Any findings will be addressed immediately. The policy titled Discharge Planning was revised in 8/2024, and was reviewed and revised currently with no changes needed. Director of Social Work will be educated on the above policy by the Corporate Director of Social Work, with emphasis on asking residents (and/or resident representatives, when appropriate) about their discharge planning wishes on admission, readmission, and at least quarterly, on making timely referrals for transfer/discharge requests, on documenting discharge planning efforts, and on communicating updates to the resident (and/or representative when appropriate). The IDT will discuss upcoming discharges, lateral transfer requests, and any discharge planning status changes at morning report daily. The Director of Social Work will utilize a Discharge Planning Tracking Tool to monitor the discharge planning and communication status of residents requesting discharge planning. The Administrator /designee will audit the medical record of a sample of 5 residents with discharge or transfer plans/requests weekly x4 weeks, then 5 residents monthly X 3 months, to ensure the requested discharge planning efforts have been made, documented, and communicated with the resident (and/or resident representative, when appropriate). All findings will be brought to the facilitys QA Committee monthly for review and recommendations. Responsible party: Administrator/Designee |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure each resident received and the facility provided food prepared in a form designed to meet individual needs for 1 of 1 resident (Resident #383) reviewed. Specifically, Resident #383 had a physician order [REDACTED]. A written order was required. The food and nutritional services department was responsible for preparing and serving the diet texture and fluid consistency as ordered. The facility diet manual documented nectar thick liquids consistency was syrup like and coated a spoon. Resident #383 had [DIAGNOSES REDACTED]. The resident was admitted during the evening on 9/23/2024. The 9/23/2024 hospital discharge summary documented Resident #383 was evaluated by a speech language pathologist for ongoing dysphagia which was present prior to admission. The resident was mostly nonverbal at baseline secondary to [MEDICAL CONDITION] and a traumatic subdural hematoma (collection of blood between the brain and skull) following a fall in (MONTH) 2024. The resident underwent [REDACTED]. Their swallow was severely delayed, and their pharyngeal musculature was very weak. It was recommended to continue a pureed and nectar thick diet. The physician #9 9/23/2024 admission orders [REDACTED]. During an observation on 9/24/2024 at 8:24 AM, Resident #383 was in their room in bed with their breakfast tray. Their family member asked Physical Therapist #17 who was in the hall, why Resident #383 had thin liquids when they had nectar thick liquids in the hospital until their discharge yesterday evening. Physical Therapist #17 stated they would look into it and get back to the family member. The meal ticket documented a pureed diet only. There was no documentation of nectar thick liquids. Physical Therapist #17 returned and stated they checked with the nurse and Resident #383 was ordered nectar thick liquids and they removed all the thin liquids from the resident's tray before the resident drank. The resident's breakfast meal ticket dated 9/24/2024 documented nectar thick orange juice, nectar thick skim milk, nectar thick coffee, and nectar thick water. During an interview on 9/24/2024 at 8:56 AM, Resident #383's family member stated the resident was in the hospital following a tractor rollover, they were recovering from multiple broken bones, and they underwent a swallowing evaluation before being admitted to the facility. After the swallowing evaluation the family member was told Resident #383 was silently aspirating (inhaling food or liquids in the lungs). They visited the resident last evening after dinner was served and did not observe the meal served to the resident. During an interview on 9/24/2024 at 9:40 AM, Certified Nurse Aide #30 stated the wrong tray was given to Resident #383 that morning. During an interview on 9/25/2024 at 12:29 PM, Licensed Practical Nurse #31 stated when there was a new admission, orders were sent from the hospital to the facility for review and the orders were entered before the resident arrived. Orders were entered by the admitting licensed practical nurse which included diet orders. After the diet was ordered they thought the order went to the kitchen and the registered dietitian, and the meal ticket was printed by the front desk attendant and given to the kitchen staff. During an interview on 9/25/2024 at 12:53 PM, Licensed Practical Nurse Unit Manager #32 stated they were notified of the pending admissions every morning. The hospital called report to the unit nurse and the admission assessment was completed by them or the unit licensed practical nurse and a diet was ordered. Director of Food Services #33 picked up the diet order and ensured each resident received the correct diet. They stated Resident #383 arrived at the facility on 9/23/2024 at approximately 5:00 PM and was ordered a pureed nectar thick diet because they had swallowing problems at the hospital. They were unsure what diet consistency Resident #383 received for dinner on 9/23/202 or how the resident received the wrong fluid consistency for breakfast on 9/24/2024. They stated it was important for the resident to get the right consistency because they could choke and get pneumonia. During an interview on 9/25/2024 at 3:16 PM, Physical Therapist #17 stated they were working in the morning on 9/24/2024 when they were notified by a family member that Resident #383 had the wrong fluid consistency on their tray. They looked at the meal ticket which documented regular pureed. If the resident was on nectar thick liquids the meal ticket would document puree/nectar, however the ticket did not document nectar thick liquids. They asked Licensed Practical Nurse #14 who confirmed the resident was ordered nectar thick liquids. Physical Therapist #17 stated they removed all the thin liquids which included coffee, orange juice, and milk from the resident's tray. They stated if a resident received the wrong consistency they could aspirate and get pneumonia. During an interview on 9/26/2024 at 9:30 AM, Food Service Director #33 stated they were notified of new admissions during their morning meeting. After residents arrived at the facility, they were notified by the receptionist in an email. They stated Resident #383 arrived at the facility at approximately 5:00 PM, and there was no diet order in the system, so they asked a nurse on the unit for the diet order. They were unsure what nursed told them the resident was on a pureed diet. They stated the nurse did not tell them the resident was on nectar thick liquids, they did not ask, but they should have. They stated Resident #383 received thin liquids on their 9/23/2024 dinner tray and on their 9/24/2024 breakfast tray. They stated the resident could have choked if they consumed the wrong consistency liquids. During an interview on 9/26/2024 at 10:54 AM, Assistant Director of Nursing #3 stated nurses were responsible for checking the meal ticket to ensure the resident had the correct consistency. They stated they expected all residents to receive the correct consistency on their meal tray and if they did not, the resident could choke and get pneumonia. 10NYCRR 415.14 (d-e) | Plan of Correction: Approved October 15, 2024 Resident #383 was assessed by Provider for unknown consumption of incorrect consistency and no adverse effects found. A Registered Dietitian reviewed other residents on thickened liquids and no other issues noted. Tray tickets were reviewed and no changes to diet orders noted. No other resident identified as a result of this finding. Dietary Communication Form was reviewed and no changes made. Nursing and dietary will be educated on How to process a diet order policy. Diet orders will be confirmed when a new resident is admitted . The Registered Dietician or designee will review admission diet orders for accuracy weekly x 4 weeks then monthly x 3 months to ensure residents on thickened consistencies receive and are served accurate trays. Any issues will be immediately addressed. Results of the audits will be brought to the QA committee monthly for review and input. Responsible Party: Food Service Director/Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details Based on observation, record review, and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure food was stored, prepared, distributed, and served in accordance with professional standards for food service safety for 1 of 1 main kitchen. Specifically, in the main kitchen food was not maintained at proper temperatures, there was outdated food, and the dishwasher was not in proper working order. Findings include: The facility policy, Cleaning Standards, revised 1/2023, documented high standards of cleanliness and sanitation would be defined and maintained. Cleaning was defined as the use of water, chemicals, and elbow grease to remove all food and debris from equipment and work services. Sanitizing was the use of chemicals or temperature to kill microorganisms remaining on surfaces after they have been cleaned. The facility policy, Food Storage, revised 5/10/2024 documented sufficient food storage facilities were provided to keep foods safe, wholesome, and appetizing. Food would be stored in an area that was clean, dry, and free from contaminants. Food would be stored at appropriate temperatures and by methods designed to prevent contamination or cross contamination. The facility policy, Rapid Cooling of Food, revised 1/2023 documented time/temperature for food safety would be maintained at temperatures >135 or cooled to temperatures 40 degrees or below. Time/temperature control for food safety including meats, eggs, poultry, seafood, cut melon, milk, yogurt, and cottage cheese pose a risk for growth of harmful pathogens when kept in temperature danger zones for greater than 4 hours. The procedure documented the following: - do not cover until cooled - measure temperature of product at final temperature then record; record time reached to 135 degrees. After 60 minutes record temperature. At the second hour product should have been at or below 70 degrees, if not obtained, product must be discarded. Record time, temperature and initial for each hour up to the 6th hour or until the product reached 40 degrees or below. Scrambled Eggs: During an observation on 9/24/2024 at 11:42 AM scrambled eggs in a closed one-gallon plastic container were in the reach in cooler and were labeled with the date of 9/24. The eggs were measured at 94 degrees Fahrenheit. During an interview on 9/24/2024 at 12:10 PM, Cook #44 stated the cooked scrambled eggs were put into the reach in cooler right after breakfast which was between 8:30 AM and 9:00 AM. The stated they did not check the temperature of the eggs or monitor them after they were put into the cooler. The leftovers were usually used for the pureed option on the next day's meal service. Meat could be left out after it was cooked to cool down slowly for about 2 hours, but they did not remember the cooling requirements after that. They did not document the cooling process and they were not aware the eggs needed to be cooled properly. During an observation and interview on 9/24/2024 at 12:16 PM, the scrambled eggs were measured by the surveyor and Cook #44 at 87 degrees Fahrenheit. Cook #44 stated the scrambled eggs were not cooled properly and they would voluntarily discard the eggs. During an interview at 9/24/2024 at 12:26 PM, Food Service Director stated cooling was done by cutting in half large roasts or icing it down to get to a temperature or below 41 degrees Fahrenheit. They stated the cooling time was completed within four hours; however, they were not sure. They stated the scrambled eggs that were measured over 90 degrees Fahrenheit and were in the cooler for over three hours, did not meet the cooling requirements, and should have been discarded. Improper cooling/cold holding turkey salad: During an observation and interview on 9/24/2024 at 11:46 AM, there was a large bowl of turkey salad located in the walk-in cooler covered with multiple layers of plastic wrap which measured at 49.6 degrees Fahrenheit. The Food Service Director stated it was made by Cook #44. During an interview on 9/24/2024 at 12:04 PM, Cook #44 stated they made the turkey salad approximately 30 minutes ago. They ground the turkey in a food processor, added mayonnaise from the walk-in cooler, mixed it together in a bowl, covered it with plastic wrap, and returned it to the walk-in cooler. They stated it should be cooled to the proper temperature, and the proper temperature was the walk-in cooler temperature, but they were not sure what that numerical temperature was. They stated they took and documented food temperatures during and after cooking, but they did not document or measure a temperature of the turkey salad. When food needed to be cooled down quickly, they used an ice bath, however, they were not sure the time limit required to properly cool food. During an observation and interview on 9/24/2024 at 12:22 PM, the temperature of the turkey salad was remeasured with Cook #44 and measured at 49.5 degrees Fahrenheit. Cook #44 stated the turkey salad was not cooling properly. The product was uncovered and moved to the walk-in freezer to rapidly cool the product for today's dinner meal. During an interview and observation at 9/24/2024 at 12:26 PM, the Food Service Director stated the turkey salad was not cooled properly because it did not change temperatures after being in the cooler for nearly one hour. During an observation on 9/24/2024 at 1:33 PM, the temperature of the turkey salad was measured with Cook #44 at 40 degrees Fahrenheit. Corporate Registered Dietitian #45 was showing Cook #44 how to complete a cooling log sheet. Outdated food in the kitchen: During an observation on 9/24/2024 at 11:42 AM, a closed one-gallon plastic container located in the reach in cooler located opposite the walk-in cooler contained cooked rice that was labeled with the date 9/20/2024. During an interview on 9/24/2024 at 12:18 PM, Cook #44 stated the leftover rice had been in there for more than three days and should have been discarded. During an interview at 9/24/2024 at 12:26 PM, the Food Service Director stated leftovers were discarded after three days and the rice should have been discarded. They stated they were responsible for checking the coolers along with the cooks, and this process was not documented. Unclean and uncleanable surfaces/ steam table in disrepair/ dishwasher out of service: During an observation and interview on 9/23/2024 at 10:34 AM the main kitchen steam table had no lights to signify that it was functioning, and the front service rail bars of the steam table were taped in the corners (not smooth and easily cleanable). The front of the oven doors had dried debris on them, the handles on the sink were dripping, the basement dry food storage area had a box with folded boxes in an area near the entry door, and there was an unsanded and unpainted dry wall patch on the left wall near the hallway entrance approximately 1-foot by 1-foot. The Food Service Director stated they recently discussed concerns about the steam table to maintenance and Administration about it needing to be fixed or replaced. During an interview on 9/25/2024 at 3:22 PM the Administrator stated they were aware the dishwasher was broken, and disposable plates and utensils were used during that time. They called 3 different contractors, and one was able to get the parts needed to repair it. Additionally, the steam table lights not working were not a major concern if staff was taking temperatures of food prior to, during, and after meal services. The surgical and duct tape and zip ties holding together the tray line bars were not cleanable surfaces and would be corrected soon. During an interview on 9/26/2024 at 10:09 AM the Director of Food Services #33 stated when the dishwashing system was not functioning properly, they notified maintenance and the Administrator. 10NYCRR 415.14(h) | Plan of Correction: Approved October 15, 2024 Scrambled eggs were discarded on 9/24. Turkey salad was uncovered and moved to walk-in freezer to rapidly cool on 9/24. Cooked rice was discarded on 9/24. Cook #44 was educated on proper cool down procedures. The rail bars of the steam table were repaired and tape was removed, the oven doors were cleaned, the sink handles were repaired, and the box in dry storage was removed. Dishwasher machine was repaired by vendor. The facility recognizes that all residents that eat by mouth can be potentially affected by this deficient practice however, none was found to be affected. The facility policy and procedure titled Rapid cooling of food was reviewed. No revisions were required. The facility policy and procedure titles Food temperature policy was reviewed. No revisions were required. The facility's policy and procedure titled Equipment failure and Repair was reviewed. No revisions were required. All dietary staff will be educated on proper food storage to maintain safe food temperatures. All dietary staff will be educated on proper cool down procedures. All dietary staff will receive education to immediately report any areas in disrepair to be evaluated by the maintenance department. Kitchen sanitation audit was updated to include monitoring the steam table rails and sink handles for proper functionality. The Food Service Director will complete a kitchen sanitation audit weekly x 4 weeks, then monthly until substantial compliance. The Food service director will report outcomes from audits monthly with interventions to QAPI committee monthly. The need for continued reporting will be determined by the QAPI committee. Responsible Party: Food service Director/ Administrator |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification and abbreviated (NY 293 and NY 801) surveys conducted 9/23/2024-9/26/2024, the facility did not ensure each resident received adequate supervision for 1 of 2 residents (Resident #1) reviewed for falls. Specifically, Resident #1 was transferred without the use of a lift device as planned. The facility policy, Therapy Services, created 10/12/2021, documented therapy services would conduct a comprehensive patient centered evaluation which included the development of a plan of care with appropriate interventions to reach specified resident goals. The facility policy, Lift-Full Body Mechanical Lift, last reviewed 8/20/2023, documented at a minimum, two trained staff members were needed to safely move a resident with a floor based full body mechanical lift. Resident #1 had [DIAGNOSES REDACTED]. The 8/2/2024 Minimum Data Set assessment documented the resident had moderately impaired cognition, was dependent on staff for all transfers, and had one fall. The comprehensive care plan initiated 7/7/2021 documented the resident required assistance with activities of daily living and was at risk for falls. Interventions included use of a sit to stand mechanical lift for all transfers. The 6/28/2024 Physical Therapist #12 Physical Therapy Discharge Summary documented the resident used the stand pivot disc for bed to wheelchair transfers. The Kardex (care instructions) documented the resident required a sit to stand mechanical lift for transfers. During an observation on 9/24/2024 at 2:00 PM Resident #1 was in their wheelchair in their room calling out for assistance. Certified Nurse Aide #24 stopped outside their door and asked the resident what they needed. When the resident stated they needed to be changed, Certified Nurse Aide #24 entered the room without any lift device and closed the door. At 2:06 PM, Certified Nurse Aide #24 exited room without a lift and the resident was lying in their bed. There was no lift device observed in the resident's room. During an observation on 9/25/2024 at 10:50 AM a lift device was not observed in Resident #1's room. Resident #1's visitor informed Licensed Practical Nurse #6 the resident was sitting in their wheelchair and needed to be changed. Licensed Practical Nurse #6 asked for the assistance of a certified nurse aide. Both Licensed Practical Nurse #6 and the certified nurse aide entered the room without a lift device. At 10:57 AM, Licensed Practical Nurse #6 brought the resident out of their room in their wheelchair followed by the certified nurse aide. Neither brought a lift device out of the room and there was not one observed in the resident's room. During an observation on 9/25/2024 at 12:52 PM, a visitor returned Resident #1 to their room in their wheelchair. At 1:30 PM the resident's family requested the resident be changed. Certified Nurse Aide #15 entered the resident's room without a lift device. The resident was in bed, Certified Nurse Aide #15 was in the bathroom, and there was no lift device in the room. During an interview on 9/24/2024 at 2:27 PM, Certified Nurse Aide #24 stated the transfer status of a resident was found in the computer kiosk and was checked every shift before they started working. A mechanical lift transfer always required the assistance of two staff for safety of the residents and to prevent falls. One person was needed to hold the lift and the other to hold the resident. Staff should only transfer residents according to what was documented on their care instructions. Resident #1 was independent with transfers a couple months ago, but after a fall and a broken hip they were changed to assist of 1 for transfers. During an interview on 9/25/2024 at 10:20AM, Resident #1 stated staff did not use a lift device to transfer them in and out of bed but used the resident's arms to transfer. During an interview on 9/25/2024 at 1:00 PM, Licensed Practical Nurse #6 stated resident's transfer status was documented in the care plan and on the task list. Therapy determined the transfer status of the residents. Transfer status was checked every day for changes and should always be followed. If a recommendation was for a sit to stand, it would not be appropriate to transfer a resident without the use of it. The facility had Hoyer lifts (a brand of a mechanical lift) and a mechanical sit to stand. The use of any lifting device required the assistance of two people. Resident #1 required assistance of two to stand pivot transfer, but a lift could be used if the resident was having difficulty. It was important that therapy's transfer recommendations were followed as the resident and staff could get hurt. During an interview on 9/25/2024 at 3:13 PM, Licensed Practical Nurse Manager #22 stated therapy determined a resident's transfer status. Those recommendations were communicated to nursing, who then updated the care tasks and care instructions. They expected the nurse aides to check the care instructions every time prior to the start of their shift. The facility had a Hoyer and a stand pivot disc, but not a mechanical sit to stand. All three devices required the assistance of two when used. Staff was allowed to use more assistance than required in the care plan, however, could not use less assistance than was documented in the care plan. Resident #1's therapy recommendation from 4/19/2024, indicated the resident required the use of a mechanical sit to stand lift. There was a handwritten notation to use stand pivot disc for transfers. Staff should use the stand pivot disk when transferring the resident. If therapy recommendations were not followed a resident could be injured. During an interview on 9/26/2024 at 9:14 AM, Physical Therapist #23 stated the facility currently used Hoyer lifts and a stand pivot disc. There was a mechanical sit to stand that was not functioning and had been in the basement for about six months. The mechanical sit to stand provided more assistance to the resident than the stand pivot disc. The stand pivot disk could be used on the unit by the certified nurse aides and required the assistance of 1 or 2 people and a gait belt. Physical therapy's transfer recommendations should be followed to provide consistency and to prevent falls or injuries. Resident #1 once used a four wheeled walker, but after a fall, therapy's recommendation changed to stand pivot disc with gait belt assistance of two. There had been no recent changes in the resident's status that had been reported to them and it was not safe to transfer the resident with assistance of one. During an interview on 9/26/2024 at 11:42 AM, the Director of Nursing stated transfer status was in the care plan and care instructions and should always be followed unless changed by therapy. The facility had Hoyer lifts and a stand pivot disk and staff were educated on their use. There was not a mechanical stand lift in the building. The stand pivot disk required assistance of two and provided less support than the mechanical sit to stand. The two were not interchangeable. Resident #1's had a history of [REDACTED]. They expected staff to verify this because the mechanical sit to stand lift was not available. If the resident was care planned for a lift device, staff should be using it. It was not okay to transfer the resident with assistance of one or without the recommended device as falls, shoulder injuries, and staff injuries could occur. 10 NYCRR 415.12(h)(1)(2) | Plan of Correction: Approved October 25, 2024 Resident #1 was referred to therapy for transfer status clarification. Therapy determined that the appropriate transfer status for Resident #1 is substantial assist of 2 staff using the stand pivot disc. Care plan and Tasks updated to reflect. CNA #15 and CNA #24 received 1:1 education regarding following the Kardex for all care tasks. Therapist #23 received 1:1 education on filling out therapy recommendation communication form properly regarding the stand pivot disc. All residents using the stand pivot disc for transfers tasks were reviewed for accuracy. Issues noted were corrected immediately. All nursing staff (CNA/LPN/RN) were educated on following Kardex care instructions for transfer tasks. All therapy staff were educated on filling out therapy recommendation form properly. DON or designee will audit all therapy transfer recommendations and ensure accuracy prior to entering into tasks and care plan weekly for 4 weeks. Then monthly for 3 months. Results will be brought to the QAPI Committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI Committee is achieved. Responsible Party: Director of Nursing |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews, during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure residents with limited range of motion received appropriate treatment and services to prevent further decrease in range of motion for 2 of 2 residents (Resident #7 and #15) reviewed. Specifically, Residents #15 and #7 resting palm (hand) guards were not applied appropriately as recommended by occupational therapy for hand and finger contractures (shortening of muscle or tendons preventing normal movement). Findings include: The facility policy, Appliances- Splints, Braces, Slings, revised 4/2019 documented to protect the safety and well-being of residents, and to promote quality care, the facility used appropriate techniques and devices for appliances, splints, braces, and slings; nursing would ensure certified nurse aide staff knew the proper application and removal of appliances; and nursing would ensure the appropriate sign off of appliance task options. 1) Resident #15 had [DIAGNOSES REDACTED]. The 6/30/2024 Minimum Data Set documented the resident had impaired cognition, functional limitation of the upper extremity, did not refuse care, and required maximum assistance for most activities of daily living. The Comprehensive Care Plan initiated 3/4/2021 documented the resident had limited physical mobility related to gait and mobility abnormalities. Interventions included a left palm protector on at all times except during functional tasks. The resident's Kardex (care instructions) documented left palm protector on at all times except for functional tasks. The 7/30/2024 Occupational Therapy Evaluation and Plan of Treatment by Occupational Therapist #13 documented Resident #15 had a left-hand contracture and during prior therapy sessions from 6/12/2024-7/3/2024 the resident received services to decrease the contracture in their left hand that included a palm protector splint. The resident was observed in their room without a left palm protector on 9/23/2024 at 11:14 AM, 9/24/2024 at 8:34 AM, 9/24/2024 at 12:48 PM, and 9/25/2024 at 9:08 AM. During an interview on 9/25/2024 at 11:13 AM, Certified Nurse Aide #25 stated certified nurse aides applied splints and documented in the task section of the electronic record. If splints were missing or the resident refused, it was reported to the nurse. Resident #15's resident care instructions listed a left palm guard at all times but was not listed as a task they could sign off on. Splints were important to prevent contractures. If a splint or guard was recommended but not used, the resident's contractures could worsen. During an interview on 9/25/2024 at 1:00PM, Licensed Practical Nurse #6 stated certified nurse aides applied splints and if there was a problem applying them it should be reported to the nurse and documented. Splints required an order and were on the treatment administration record for signatures. They were not aware Resident #15 had a recommendation for palm guards. The 9/2024 Treatment Administration Record did not document the use of a palm protector splint. During an interview on 9/25/2024 at 3:13 PM, Licensed Practical Nurse Manager #22 stated therapy evaluated residents for contractures. If a splint was recommended, nursing was informed so the resident's care instructions and care plan could be updated and a task for the aides to document created. Certified nurse aides applied splints and palm guards and any issues or refusals were reported to the nurse and documented. Palm guards were used for hand contractures and should be worn as recommended. If not, open areas, worsening of contractures, and pain could occur. Resident #15 had contractures of their hands and should have a left palm guard on at all times except during functional tasks. This was listed on the resident's care instructions and as a task, however, the task did not allow the certified nurse aides to sign off on. During an interview on 9/26/2024 at 9:14 AM, Physical Therapist #23 stated the therapy department evaluated residents and when splints were recommended, they informed nursing so the care plan could be updated. They expected their recommendations to be implemented and any issues should be reported to them. Resident #15 had hand contractures and a hand guard was recommended. Palm guards were effective in maintaining current range of motion, keeping hands clean, and preventing skin integrity issues that could be caused by fingernails coming into contact with palms. During an interview on 9/26/2024 at 11:42 AM, the Director of Nursing stated therapy made recommendations for splints and palm guards and anyone who had a recommendation should have a task associated with the splints allowing the certified nurse aides to document in the electronic record. Any refusals should be reported to nursing to verify and document. Resident #15 had a left palm guard listed in their care instructions and as a task, however the task had not been activated properly resulting in the certified nurse aides being able to see the task, but not being able to document the task. They felt staff should have asked and verified whether the guards should be put on or not. If palm guards were not applied per recommendations contractures could worsen and skin breakdown could occur. 2) Resident #7 had [DIAGNOSES REDACTED]. The 7/17/2024 Minimum Data Set documented the resident had severe cognitive impairment, did not refuse care, had functional limitation in range of motion in both arms, and was dependent for most activities of daily living. The Comprehensive Care Plan initiated 4/26/2021 documented the resident had limited physical mobility related to deconditioning, [MEDICAL CONDITION]'s disease, and functional [MEDICAL CONDITION] (inability to move arms and legs). Interventions included bilateral palm guards at all times except during hygiene care. The 10/16/2023 Occupational Therapy Evaluation and Plan of Treatment by Occupational Therapist #13 documented Resident #7 had impaired range of motion in the wrists, hands, and all fingers and recommended that finger separators and a palmer guard was worn on both hands at all times except during bathing and exercise. The 11/3/2023 Occupational Therapy Discharge Summary by Occupational Therapist #13 documented the resident's goal of maintaining tolerance for bilateral palm protectors 24 hours a day with periodic skin assessment was met on 10/27/2023. Resident #7's Kardex (care instructions) documented bilateral palm guards on at all times, remove for hygiene. Resident #7 was observed in their room without palm guards on their right and left hands on 9/23/2024 at 11:08 AM, 9/24/2024 at 8:34 AM, and 9/24/2024 at 1:29 PM. During an interview on 9/25/2024 at 11:13AM, Certified Nurse Aide #25 stated Resident #7 had contractures but did not believe the resident wore splints because they had never seen the resident with them. The resident's care instructions included bilateral palm guard at all times but was not listed as a task for the aides to sign for. During an interview on 9/25/2024 at 1:00PM, Licensed Practical Nurse #6 stated they were not aware Resident #7 had a recommendation for palm guards. During an interview on 9/25/2024 at 3:13 PM, Licensed Practical Nurse Manager #22 stated Resident #7 was very stiff and had bilateral palm guards listed in their care plan, in their resident care instructions, and as a task. The task did not allow the certified nurse aides to document in the electronic record. During an interview on 9/26/2024 at 9:14 AM, Physical Therapist #23 stated Resident #7 had hand contractures and palm guards were recommended. The only compliance issue they were aware of occurred 3 months ago when the guards were reported missing and was resolved when they were found in the laundry. During an interview on 9/26/2024 at 11:42 AM, the Director of Nursing stated Resident #7 had hand contractures and bilateral palm guards listed in their care instructions and as a task, however the task had not been activated properly resulting in the certified nurse aides being able to see the task, but not being able to document the task. Staff should have asked and verified whether the guards should be put on or not. Residents that were ordered palm guards and did not wear them could have worsening of contractures and skin breakdown. 10NYCRR 415.12(e)(2) | Plan of Correction: Approved October 15, 2024 Resting palm guard was applied to Resident # 7. Care plan and tasks reviewed to ensure it is placed in those as well. Resting palm guard was applied to Resident #15. Care plan and tasks reviewed to ensure it is placed in those as well. All resident using resting palm guards were audited for placement. No issues were found at the time of the audit. All nursing staff (CNA/LPN/RN) was educated on appropriate application of resting palm guards as recommended by occupational therapy for hand and finger contractures. DON or designee will audit all residents using resting palm guards for appropriate placement as recommended by occupational therapy weekly for 4 weeks. Then monthly for 3 months. Results will be brought to the QAPI Committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI Committee is achieved. Responsible Party: Director of Nursing |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review and interview during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not provide the appropriate liability and appeal notices to Medicare beneficiaries for 1 of 3 residents (Resident #72) reviewed. Specifically, Resident #72 remained in the facility after discontinuation of Medicare Part A services and the facility did not provide the resident with a Skilled Nursing Facility Advanced Beneficiary Notice of Non-Coverage (Centers for Medicare and Medicaid Services- ) for Medicare Part A as required. Findings include: The facility policy, Notice- Advances Beneficiary Notice, dated 7/2019 documented the Advance Beneficiary Notice of Non-coverage was to be issued by the facility where Medicare payment was expected to be denied. The notice must be provided within enough time to provide the beneficiary enough time to make an informed decision on whether or not to continue to receive services and accept potential financial liability not covered by Medicare. The notice must give a brief explanation why the beneficiary's needs did not meet Medicare coverage guidelines. The Center for Medicare and Medicaid Services form instructions for the Skilled Nursing Facility Advanced Beneficiary Notice of Non-coverage Center for Medicare and Medicaid Services- , expiration date 1/31/26, documented a Skilled Nursing Facility Advanced Beneficiary Notice of Non-coverage (form ) must be issued by providers to beneficiaries in situations where Medicare payment was expected to be denied. The Skilled Nursing Facility Advanced Beneficiary Notice of Non-coverage must be delivered far enough in advance that the beneficiary or representative had time to consider the options and make an informed choice prior to services ending. Resident #72 had [DIAGNOSES REDACTED]. The 9/17/2024 Minimum Data Set assessment documented it was a Skilled Nursing Facility PPS (Prospective Payment System) Part A Discharge (end of stay) assessment with a start date of 7/1/2024 and an end date of 9/17/2024. The Skilled Nursing Facility Advanced Beneficiary Notice of Non-coverage Center for Medicare and Medicaid Services- letter documented Resident #72's effective end date of services was 9/17/2024. Business Office Manager #16's handwritten note documented the form was mailed to the resident's representative as the resident was unable to sign for themselves (no date documented when the form was mailed). The letter was not dated. The United States Postal Service Certified Mail Receipt addressed to the resident's representative did not document a date the letter was mailed by the facility. During an interview on 9/25/2024 at 4:21 PM, Business Office Manager #16 stated they sent the beneficiary letters as soon as the insurance company or therapy notified them of a pending cut from therapy. They should have put a date on the letter and certified mail forms when it was sent by the facility. There was no tracking mechanism by the facility. The resident remained in the facility and the facility charges were back dated and covered by Medicaid. The manager stated they should have documented when the letter was sent as it was to be sent at least 2 days prior to termination of services. During a telephone interview on 9/25/2024 at 4:30 PM, Resident #72's representative stated they received the beneficiary letter on 9/23/2024 from the post office and signed that the letter was received. The representative stated they would have appealed the non-coverage if they were aware earlier. They made numerous attempts to contact the facility regarding the reason for the discontinuation of services, and the facility had not called them back or given them an explanation as to why the resident was cut from therapy. 10 NYCRR 483.10 (g) (18) | Plan of Correction: Approved October 15, 2024 Certified mailed letter to resident #72 POA was uploaded day it was mailed out, but cannot retroactively date already sent mail. All residents that are discharged from Med A can be affected. Education given to Business Office Manager on proper Nomnc procedures including timely distribution of Nomnc when resident is unable to sign. Education will be given by the regional BOM or regional director of clinical reimbursement. Current Nomnc policy and procedures does not need any revisions. Regional director of clinical reimbursement or designee will audit all Med A discharges weekly x4 weeks and then monthly x3 months. Results will be brought to QAPI on a monthly basis. Responsible Party: Administrator/Regional Director of Reimbursement |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details Based on observation and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure each resident received food and drink that was palatable, flavorful, and at an appetizing temperature for 3 of 3 meals (the 9/24/2024 lunch meal, the 9/25/2024 special Fall festival meal, and the 9/25/2024 lunch meal) reviewed; for 7 of 7 anonymous residents present at the Resident Council meeting; and for 2 additional residents interviewed (Residents #178 and #180). Specifically, the 9/24/2024 and 9/25/2024 lunch meals were not flavorful; the 9/25/2024 Fall festival meal was not served at palatable and appetizing temperatures; 7 of 7 anonymous residents at the Resident Council meeting stated the food was often not appetizing and served cold; and 2 residents (Resident #178 and #180) stated the food was not flavorful and was served cold. Findings include: The facility policy, Rapid Cooling of Food, revised 1/2023, documented temperature control for food safety would be maintained at a temperature greater than 135 degrees Fahrenheit or cooled to a temperature of 40 degrees Fahrenheit. During an interview on 9/23/2024 at 11:25 AM, Resident #178 stated the food was bland, did not taste good, and was served cold. During an interview on 9/23/2024 at 11:42 AM, Resident #180 stated the food had an unpleasant taste and texture and was usually served cold. During a resident group interview on 9/23/2024 at 1:32 PM, 7 anonymous residents stated the food did not taste good and was not served hot. During an interview on 9/24/2024 at 9:40 AM, Certified Nurse Aide #30 stated residents complained the food did not taste good and was not served hot. During a lunch meal observation in the main dining room on 9/24/2024 at 12:04 PM, a lunch meal tray was tested . The beef stroganoff was measured at 135 degrees Fahrenheit, and the beef tasted bland and was difficult to chew due to a rubbery texture. During a Fall festival lunch meal observation in the main dining room on 9/25/2024 at 12:08 PM, a lunch meal was tested . The corn dog was measured at 100 degrees Fahrenheit, the sweet potato fries were measured at 99 degrees Fahrenheit, and the corn on the cob was bland, chewy, and mushy. During a lunch meal observation on 9/25/2024 at 12:32 PM, Resident #72's meal tray was tested , and a replacement tray was ordered. The barbeque chicken was bland, and the barbeque sauce tasted like plain ketchup. The corn on the cob was bland, chewy, and mushy. During an interview on 9/26/2024 at 9:27 AM, Activities Aide #42 stated there was miscommunication during the Fall festival meal regarding who was supposed to take the temperatures of the food that was being served. The activities department obtained the food from the kitchen, and they served it to the residents. They stated they should have taken the temperature of the food that was being served even though they used a portable stove to keep the food hot. During an interview on 9/26/2024 at 9:46 AM, the Food Service Director stated the activities and dietary department cooked the food for the Fall festival. The cook should have taken temperatures of the food but there was miscommunication between the departments, they were short staffed, and the cook was doing other jobs and not just cooking. They were unsure when the last test tray was done. The registered dietitian used to do test trays, but they were working remotely so the test trays were not being done regularly. They stated they planned to start doing them again. They usually tasted the food while it was being cooked. The cooks had recipes to follow and were not able to add salt, but used spices like garlic and pepper, and they would add salt and pepper on resident trays if they were allowed to have it. The corn dogs and sweet potato fries were not hot enough and should have been served at a minimum of 140 degrees Fahrenheit and the food served to the residents should always be palatable. During an interview on 9/26/2024 at 10:13 AM, the Director of Activities stated the food for the Fall festival was reheated using a portable stove after it was cooked. The cook took the food temperatures when it came out of the oven and told them the temperatures were okay. They were unsure what temperature the food should have been kept at and normally the kitchen staff would have helped, but they were short staffed. 10NYCRR 415.14(d)(1)(2) | Plan of Correction: Approved October 15, 2024 Food Service Director met with Resident #178 and #180 to review meals and ensure food served at palatable temperatures. Temperatures and palatability of meals were monitored on both units by the Food Service Director or designee and any concerns identified were addressed immediately. The facility recognizes that all residents that eat by mouth can be potentially affected by this deficient practice. The facility's policy and procedure titled Food Temperature Policy was reviewed and no changes were made. Foodservice staff will receive education on Food temperature policy to ensure staff monitor food temperatures at point of service as to allow it to be transported and delivered at palatable temperatures. Test tray evaluation was reviewed and no changes were made. The Food Service Director or designee will address meal palatability and food temperatures at the monthly food council meeting. The Food Service Director or designee will evaluate and monitor the temperature on 3 trays per week x 4 weeks, then 3 trays per month x 3 months or until substantial compliance is met. The Food service director will report outcomes from food committee meeting monthly with interventions to QAPI committee monthly. The need for continued reporting will be determined by the QAPI committee. Responsible Party: Food service Director/ Administrator |
Scope: N/A
Severity: N/A
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details Based on observation, record review, and interviews during the recertification survey conducted 9/24/2024-9/26/2024, the facility did not document quarterly inventory reviews of emergency supplies under Public Health Law 2803-12. Specifically, there was no documented evidence the facility conducted quarterly inventory of the emergency 72-hour water and food supply from the second quarter of 2023 to the first quarter of 2024 as required by New York State. Findings include: There was no documented evidence quarterly inventories of the facility's emergency water and food supply were completed from the second quarter of 2023 to the first quarter of 2024. The emergency food and water were not inventoried between (MONTH) 2023 and (MONTH) 2024. During an observation on 9/26/2024 at 12:45 PM, the facility had a 72-hour emergency water and food supply in the basement dry storage room. This room contained emergency dry food supplies and approximately 312 gallons of emergency water. During an interview on 9/25/2024 at 5:58 PM, the Administrator stated they were aware that the emergency food and water inventories were required to be checked quarterly and the facility had been checking this monthly. They stated the existing emergency food and water supply were rotated quarterly and checked for expiration dates. They were unable to locate any monthly emergency food and water inventories between (MONTH) 2023 and (MONTH) 2024. They stated it was important all food and water were safe for residents and staff. PHL 2803-12(a) | Plan of Correction: Approved October 15, 2024 A quarterly inventory of the 72-hour emergency supplies of food and water has been documented. The facility recognizes that all residents have the ability to potentially be affected by this deficient practice. Education provided to Food Service Director related to conducting a documented quarterly inventory of the 72-hour emergency supply of food and water. Food Service Director will conduct a documented quarterly audit for the next 6 months of the 72-hour emergency supply of food and water. All findings will be submitted to the facilitys QAPI Committee for review and recommendations. Responsible party: Food Service Director |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure residents received treatment and care in accordance with professional standards of practice, the comprehensive person-centered care plan, and the resident's choices for 1 of 1 resident (Resident #178) reviewed. Specifically, Resident #178's urinary catheter (tube that drains urine) drainage bag was observed above the level of the bladder. Findings include: The facility policy, Urinary Catheter Guidelines, revised 9/11/2023, documented care was provided to residents with indwelling urinary catheters to prevent, reduce the reoccurrence, manage, and resolve urinary tract infections. The urinary catheter drainage bag should be positioned below the level of the bladder and should not touch the floor. Resident #178 had [DIAGNOSES REDACTED]. The 9/19/2024 Minimum Data Set assessment documented the resident was cognitively intact, had an indwelling urinary catheter, and had a urinary tract infection within the last 30 days. The comprehensive care plan initiated on 9/14/2024 documented the resident had an indwelling urinary catheter. Interventions included maintaining the urinary drainage bag below the level of the bladder, monitor/record/report signs and symptoms of a urinary tract infection, change catheter as ordered, and urology consult as ordered. The 9/12/2024 physician orders [REDACTED]. - Indwelling urinary catheter: size16 with a 5-milliliter balloon to down drain, change as needed. The following observations of Resident #178 were made: - on 9/24/2024 at 11:13 AM, 12:31 PM, and 12:43 PM sitting in their wheelchair in their room. Their urinary catheter tubing was observed coming out of the bottom of their left pant leg, under the wheelchair, and the drainage bag was clipped to the top of the wheelchair's backrest that was level with the resident's shoulders and above the bladder. At 12:59 PM, self-propelling their wheelchair down the hallway. The urinary catheter drainage bag was clipped to the bottom of the wheelchair. The resident stated one of the nurses approached them a few minutes ago, moved the drainage bag to the bottom of the wheelchair, and told them it should not have been put on the back of the wheelchair. During an interview on 9/25/2024 at 1:26 PM, Certified Nurse Aide #35 stated urinary catheter bags should always be clipped to the side of the bed or the bottom of a wheelchair. They stated the resident was self-propelling their wheelchair in the hallway when they noticed their catheter drainage bag was clipped to the top of the wheelchair's backrest. They moved it to the bottom of the wheelchair so the urine would be able to flow better. They stated catheter drainage bags should always be placed below the level of the bladder so the urine would not backup in the tubing and cause an infection. During an interview on 9/26/2024 at 9:17 AM, Licensed Practical Nurse #20 stated they noticed Resident #178's catheter drainage bag dragging on the floor under their wheelchair on 9/24/2024, so they moved it to the top of the wheelchair's backrest. They stated they forgot to move it back because they got busy, and by the time they remembered someone had already moved it to the bottom of the wheelchair. They stated it was important to keep catheter drainage bags below the level of the bladder to prevent backflow and urinary tract infections. During an interview on 9/26/2024 at 10:25 AM, Assistance Director of Nursing #3 stated urinary catheter drainage bags should be hung on the side of the bedframe or on the bottom of a wheelchair. They stated it was important for Resident #178's catheter drainage bag to be below the level of the bladder to prevent urinary tract infections. 10 NYCRR 415.12 | Plan of Correction: Approved October 15, 2024 Resident #178 urinary drainage bag was placed below the level of the bladder. All residents with an indwelling urinary catheter were audited for placement of urinary drainage bag below the level of the bladder and immediately corrected if needed. All Nursing staff (CNA/LPN/RN) were re-educated on Urinary Catheter Guidelines to include proper placement of urinary drainage bag. DON or designee will audit all residents with urinary drainage bags 2 times weekly to ensure that the bag is below the level of the bladder for 4 weeks. Then 1 time weekly for 4 weeks. Then Monthly for 3 months. Results will be brought to the QAPI committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI committee is achieved. Responsible Party: Director of Nursing |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation, and interviews during the recertification and abbreviated (NY 460) surveys conducted 9/23/2024-9/26/2024, the facility did not ensure residents had the right to a safe, clean, comfortable, and homelike environment for 2 of 2 resident units (North and South units) reviewed. Specifically, the South unit common area had a stained carpet, four burned out lights, a broken light fixture, the unit shower was missing floor and wall tiles, and the dining room countertop was damaged; the North unit resident room [ROOM NUMBER] had a dirty floor mat that smelled of mildew and cobwebs on the wall. Findings include: The facility policy, Cleaning/Disinfecting Resident Care Items and Equipment, revised 3/13/2024, documented reusable resident care items and equipment would be cleaned and disinfected according to the current Center for Disease Control and Prevention recommendations for disinfection of healthcare facilities. The facility policy, Environmental Services: Vacuuming Carpets, revised (MONTH) (YEAR), documented if there was a stain on a carpet it was cleaned according to the carpet cleaning procedure in order to maintain a safe and sanitary environment. The following observations were made on the North unit: - on 9/23/2024 at 11:03 AM, resident room [ROOM NUMBER]'s floor mat was dirty with dried debris and crumbs. When the mat was lifted there was a smell of mildew. There was a cobweb on the wall in the corner of the room. - on 9/24/24 at 8:31 AM, resident room [ROOM NUMBER]'s floor mat had dried debris. When the mat was lifted it smelled of mildew and the floor tiles were stained. There were cobwebs in the upper and lower corner of the wall above the mat. The following observations were made on the South unit: - on 9/24/2024 at 9:56 AM, the dining room countertop was damaged/chipped and the drawers under the countertop were loose and not aligned. - on 9/24/2024 at 10:08 AM, the unit shower room had multiple missing floor and wall tiles. - on 9/24/2024 at 10:26 AM, the unit hall bathroom had a broken wall tile at the bottom of the door. - on 9/24/2024 at 10:42 AM, the unit common area had several large, stained areas in the carpet, four burned out lights, and a broken light fixture. During an interview on 9/24/2024 at 01:31 PM, Housekeeper #5 stated resident rooms should be mopped daily but they could not always be done because of short staffing. They stated floor mats were cleaned every day. If a resident was not in their room the mat was wiped down, set upright to dry, and the floor was mopped. If the resident was in their room the mat was wiped down but left in place. They stated it was important to clean the rooms and floor mats to prevent the spread of infection. During an interview on 9/25/2024 at 1:00 PM Licensed Practical Nurse #6 stated floor mats were ordered from maintenance and cleaned daily by housekeeping. If there was a small spill nursing staff should clean it, however if the floor mat required additional cleaning it was sent for a power washing. During an interview on 9/26/2024 at 10:38 AM Housekeeper #8 stated the day room rug was very stained and had not been shampooed in over one year because the porter was responsible for shampooing the rug and that position had been vacant for approximately one year. They stated the rooms had not been painted in nearly nine years. They stated the rooms and common areas were not homelike. During an interview on 9/26/2024 at 12:55 PM Maintenance Director #7 stated they were aware of the lights being out in the South unit common area. They were not aware of the other environmental concerns as there were no work orders for the shower tiles or countertops. They stated it was important to keep the environment homelike for the safety of both residents and staff. 10 NYCRR 415.29(j)(1) | Plan of Correction: Approved October 15, 2024 **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** South Unit common area carpet was shampooed. South Unit common area's 4 burnt out lights was replaced. South Unit common area broken light fixture was repaired. South unit shower missing floor and wall tiles were replaced. Bumper guard was added to dining room damaged countertop. Dirty, mildew smelling floor matt from room [ROOM NUMBER] was discarded and a new floor matt was issued. All cobwebs were removed from the wall in room [ROOM NUMBER]. Housekeeper #5 was educated on proper cleaning protocols including observing for and removing cobwebs and dirty mildew floor mats. All resident areas including south common area, north and south unit hallways, north and south unit resident rooms, north and south unit shower areas, dining room, activity room, and therapy gym were observed for stained carpet, burned out lights, broken light fixtures, missing tiles, damaged countertops, dirty-mildew floor mats, and cobwebs on the walls. Findings were corrected at the time of observation. All staff from all departments (Maintenance, Housekeeping, Nursing, Administration, Activities, Human Resources, Therapy, Social Services, Reception, Business Office, Dietary, Medical Records) have been educated on the policy and procedure to report non- functioning, broken, or dirty items or areas in the building. All maintenance and housekeeping staff was educated on proper cleaning protocols including observing for and removing cobwebs and dirty mildew floor mats. Cleaning Policy was reviewed with no revisions necessary. Maintenance Director or designee will audit all resident areas including south common area, north and south unit hallways, north and south unit resident rooms, north and south unit shower areas, dining room, activity room, and therapy gym were observed for stained carpet, burned out lights, broken light fixtures, missing tiles, damaged countertops, dirty- mildew floor mats, and cobwebs on the walls. Weekly for 4 weeks. Then monthly for 3 months. Results will be brought to the QAPI Committee monthly for a minimum of 3 months but will continue until satisfaction of the QAPI committee is achieved. Responsible Party: Administrator/Maintenance Director |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 5, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on observation, record review, and interviews during the recertification survey conducted 9/23/2024-9/26/2024, the facility did not ensure residents with pressure ulcers received the necessary treatment and services, consistent with professional standard of practice, to promote wound healing, prevent infection, and prevent new ulcers from developing for 2 of 2 residents (Residents #66 and #369) reviewed. Specifically, Resident #66 developed three facility acquired pressure ulcers, one vascular wound (caused by poor blood circulation) and had a low loss air mattress (specialty mattress used to relieve pressure and provide airflow) that was not accurately set to the resident's weight, and the resident was not turned and repositioned as care planned. Resident #379 had a foot wound and did not have their foot offloaded as planned. Findings include: The facility policy, Support Surfaces- Air mattress, created 2/2019, documented the facility provided an environment of care that promoted the highest quality of care and comfort for the residents. This included the treatment and prevention of pressure ulcers with the use of support surfaces. The motor was set to the appropriate settings per the resident assessment. For example, weight for weight. Depending on mattress type, a turning and repositioning schedule was determined. The facility policy, Skin and Pressure Injury Prevention, revised 6/27/2024, documented the facility assessed residents for risk in the development of pressure injuries and implemented preventative measures in accordance with current standards of practice. Once the assessment was conducted and risk factors were identified and characterized, a resident-centered care plan was developed and addressed the modifiable risks for pressure injuries and skin protection interventions. For a person in bed, position was changed frequently, and a pressure relieving/ redistribution device was on the bed. When in bed, every attempt was made to off load pressure to heels and interventions included placement of pillows, heel boots, or other devices as recommended by provider. 1) Resident #66 had [DIAGNOSES REDACTED]. The 9/4/2024 Minimum Data Set assessment documented the resident had severely impaired cognition, had upper extremity impairment on one side, lower extremity impairment on both sides, was dependent for assistance with toileting, bathing, dressing, bed mobility, and transfers, was at risk for developing pressure ulcers, had 4 unstageable (full thickness, depth unknown) pressure ulcers that were not present on admission, received daily pressure ulcer care, applications of ointments/ medications other than to feet, had a pressure relieving device for the bed, and did not reject care. The Comprehensive Care Plan initiated 4/26/2024 documented the resident had alteration in skin integrity with an actual unstageable pressure injury to the sacrum and left buttocks and a vascular wound to the left lower extremity. Interventions included weekly wound evaluations, dressings were monitored to ensure they were clean, dry, and intact, and the wound was monitored for changes and signs/ symptoms of infection. There were no documented interventions for pressure relief. The undated care instructions documented the resident was provided with a pressure relieving/ redistribution device on the bed and the resident was dependent on one to turn and reposition every 1-2 hours as indicated and as needed. The 8/20/2024 physician orders [REDACTED]. The 9/18/2024 Nurse Practitioner #38 progress note documented the resident was being seen as requested by nursing to evaluate their wounds. The left posterior leg vascular wound measured 5.0 centimeters x 3.2 centimeters with a pink base. The sacrum wound with undermining measured 12.1 centimeters x 10 centimeter x 4 centimeters. The new unstageable left buttocks ulcer measured 1.2 centimeters x 1.1 centimeters with 100 percent yellow base. There was also a left buttock skin abrasion, no measurements were documented. Interventions included continued use of an air mattress and signs and symptoms of wound infection were monitored. Pressure ulcers were unavoidable as the resident was comfort care, bed bound, and had poor nutrition. The 9/25/2024 Registered Nurse #39 weekly wound evaluation documented the wounds were evaluated by the wound care provider and refer to the wound care provider documentation. Interventions included turning and repositioning, heels off loaded with pillow or heel boots, and pressure relieving/ reducing device on bed. The 9/25/2024 Nurse Practitioner #38 progress note documented the resident was being seen as requested by nursing to evaluate their wounds. The left posterior leg vascular wound measured 5.3 centimeters x 3 centimeters with a pink base. The sacrum wound with undermining measured 9 centimeters x 10.4 centimeters x 2 centimeters with 2 centimeter undermining at 7 o'clock. The unstageable left buttocks ulcer measured 0.5 centimeters x 1.1 centimeters with 100 percent yellow base. The left buttock skin abrasion measured 1 centimeter x 1 centimeter. Pressure ulcers were unavoidable as the resident was comfort care, bed bound, and had poor nutrition. The (MONTH) 2024 Certified Nurse Aide activities of daily living tasks did not document the resident was turned and repositioned during their shift on 9/1/2024 day shift, 9/4/2024 night shift, 9/5/2024 day shift, 9/15/2024 night shift, 9/17/2024 day shift, and 9/18/2024 night shift. The resident's medical record contained no documentation for the appropriate settings for the pressure relieving air mattress. The Weights and Vital Summary Report documented the resident was not weighed on 9/4/2024 comfort measures-no weights. The last documented weight was 123 pounds on 8/14/2024. Resident #66 was observed; - On 9/23/2024 at 10:29 AM, 12:19 PM, and 2:08 PM, lying in bed with the low air loss mattress set to 380 pounds with the mattress pump upside down on the floor under the bed. - On 9/24/2024 during a continuous observation from 9:07 AM until 11:11 AM, lying in bed with the low air loss air mattress set to 380 pounds with the pump upside down on the floor under the bed. At 1:03 PM the low air loss mattress was set to 230 pounds. - On 9/25/2024 at 9:07 AM, lying in bed with the low air loss mattress set to 230 pounds, the pump was on the foot end of the bed with a pillow over it. At 12:03 PM, 1:19 PM, and 3:28 PM, lying in bed with the low air loss mattress set to 230 pounds and signed as checked by Licensed Practical Nurse #14. - On 9/26/2024 at 9:25 AM, sleeping in bed on their back with the low air loss mattress set to 230 pounds with the pump on the foot end of the bed. During an interview on 9/25/2024 at 1:03 PM, Certified Nurse Aide #15 stated the care instructions told them the frequency a resident needed to be turned and repositioned. The documentation did not include the frequency of turning and repositioning, just that it was completed on their shift. If there was a refusal, it would be documented as a refusal. Turning and repositioning meant they rotated what side the resident was lying on and was important for skin breakdown and discomfort. Resident #66 had wounds and it was important they were repositioned every 2 hours. The air mattress was set by the nurse per the resident's weight. During an interview on 9/26/2024 at 9:27 AM, Certified Nurse Aide #41 stated residents were turned and repositioned every few hours. This meant the resident was in different positions for wound prevention, to keep off pressure points or for wound improvement if wounds were already present. Turning and repositioning meant residents were rotated from side to back and then to the other side. Resident #66 was supposed to be repositioned every 2 hours as they had wounds. They tried to reposition the resident as often as possible, but it was often difficult due to staffing shortages so they just did the best they could. The air mattress was set to the resident's weight but as a certified nurse aide, they did not touch or even look at the settings. They reported it to the nurse if the mattress was not inflated or they noticed a problem with it. During an interview on 9/26/2024 at 9:35 AM, Licensed Practical Nurse #28 stated air mattresses were set to the weight of the resident. The setting was checked at least once per shift. They did not think it was documented anywhere. Documentation meant the settings were checked. If a resident was no longer being weighed, they would not know what the mattress should be set to. They just pushed down on Resident #66's mattress and adjusted the dial per their feeling of too soft or too hard. Resident #66 was tiny, 300 pounds was probably too hard for them, and they were not sure if the mattress set inappropriately could lead to worsening pressure. They thought if the air mattress was set to the resident's weight it would be too soft. They adjusted the setting to 180 pounds a couple days ago by going with their gut. The pump was currently set at 210ish, was missing clips to hang it on the bed frame, and it should not be in the resident's bed. They did not think the weight setting was important, just what the mattress felt like to touch. The low-pressure light was blinking so they would have to have maintenance look at it. They confirmed the air mattress was documented in the Treatment Administration record but just that the air mattress existed, not what setting they set it to. During an interview on 9/26/2024 at 10:19 AM, Licensed Practical Nurse Unit Manager #22 stated turning and repositioning meant the resident was rotated from left side to right or to their back. The purpose was to prevent skin breakdown or worsening breakdown. It was documented per shift and if it was documented, it was expected it was done at the frequency indicated on the care instructions. If a resident had an air mattress, they needed an order for [REDACTED]. Resident #66 was comfort measures only and it should be set closest to the weight last documented. Nurses should not be self-selecting settings based upon whether they thought the mattress was too hard or too soft. The resident's last documented weight was 123 pounds on 8/14/2024 and their air mattress set at 380 pounds could make their pressure worse. During an interview on 9/26/2024 at 11:28 AM, the Assistant Director of Nursing stated the certified nurse aides documented turning and repositioning every shift, not every occurrence. There was no way of knowing if the resident was turned and repositioned as care planned because there was no way to document it. It was also not known when the next turn and reposition was due. It was important for frequent turning and repositioning for wound healing and could make the wound worse if not done. Air mattresses were set to the resident's closest weight. It was important it was set appropriately so the resident did not sink into the mattress, or the mattress was not too hard. It was documented by the nurses in the Treatment Administration Record every shift. If it was documented, it meant the settings were verified and if it was not documented, it was not checked. Resident #66 had pressure sores and should be turned and repositioned. The resident's last documented weight was 123 pounds and if their air mattress was set to 380 pounds it would not help with wound healing, they would be on a very hard surface. Nurses were expected to follow orders, they had recently done a training on air mattresses. Nurses were expected to look at the dial and adjust accordingly, pushing on the air mattress was not an appropriate way to set the dial. Resident #66 would not be on their back all day if they were appropriately turned and repositioned. 2) Resident #379 had [DIAGNOSES REDACTED]. The Minimum Data Set assessment was not yet completed as the resident was a new admission. The 9/20/2024 at 7:16 PM Registered Nurse #39 Nursing Admission Evaluation documented the resident was admitted to the facility for osteo[DIAGNOSES REDACTED] of the left foot. The Comprehensive Care Plan dated 9/21/2024 documented Resident #379 was at risk for skin breakdown due to obesity and disease processes. Interventions included skin observations, compression dressing was applied, and adaptive equipment was removed when skin integrity was checked. The undated care instructions documented Resident #379's heels were offloaded with heel boots as tolerated. Resident #379 was observed on 9/24/2024: - at 9:19 AM with a heel bootie hanging from the left side of the bed and their foot resting directly on the bed, the left foot was not offloaded. - at 11:27 AM in bed and the left foot was not offloaded. The boot was on the floor at the end of the bed. The resident stated they wore the boots at home and they made their foot more comfortable. - at 2:43 PM in bed with the boot on the left foot with the foot dangled over the footboard which applied pressure to the left foot. The Certified Nurse Aide Documentation Survey Report documented heel protection: offload with pillow/heel boots/heel suspension boots as tolerated and was completed every shift on 9/24/2024 and 9/25/2024. During an interview on 9/25/2024 at 8:40 AM, Certified Nurse Aide #37 stated Resident #379 came into the facility with a heel boot because they had a wound on their left foot and continued with the heel boot after admission. The heel boot was old, worn, and dirty so they received a new one from physical therapy after admission. If they did not have the heel boot on, the wound could get worse. During an interview on 9/25/2024 at 12:29 PM, Licensed Practical Nurse #31 stated offloading boots removed pressure from areas, prevented wounds from worsening, and provided comfort. They stated Resident #379 was supposed to wear an offloading heel boot to the left foot when they were in bed as they had a wound and required staff assistance to apply the boot. During an interview on 9/25/2024 at 12:53 PM, Licensed Practical Nurse Unit Manager #32 stated care plans were individualized for each resident and completed by a registered nurse on admission. They stated offloading boots were documented on the certified nurse aide instructions. They stated an offloading boot did not require a physician order [REDACTED]. They stated if the offloading boot was not worn, the resident could have increased pain and decreased wound healing and Resident #379 had a significant wound. They expected the boot to be on at all times unless the resident refused. Resident #379 did not refuse the boot. During an interview on 9/26/2024 at 10:54 AM, the Assistant Director of Nursing #3 stated care plans were individualized for each resident and ensured the care needs for each resident were met. They did not expect heel boots to be hanging over the bed or on the floor. If the boot was not worn the resident could have decreased healing to a wound or a worsening wound. They stated Resident #379 utilized an offloading left heel boot. 10NYCRR 415.12(c)(1) | Plan of Correction: Approved October 15, 2024 Resident #66 was weighed and mattress was accurately set to residents weight. Resident #66 cannot be turned and repositioned retroactively, however moving forward Resident #66 will be turned and repositioned according to plan of care. Resident #379 heel boot was applied per plan of care. All air mattresses in use were audited to ensure they were accurately set to residents weight. All issues were corrected. All residents who required turning and positioning as part of wound treatment were audited for turning and positioning while in bed and CNA documentation was reviewed for completeness. All issues were corrected. All residents using heel boots or offloading were audited for bootie placement and/or offloading as care planned. All issues were corrected. All nursing staff (CNA/LPN/RN) was educated on pressure ulcer prevention/management including air mattress use, function, settings, turning and positioning, offloading and heel boot placement. All nursing staff (CNA/LPN/RN) was educated on importance of appropriately signing all tasks in P(NAME) record. DON or designee will audit all residents using air mattresses weekly for proper setting for 4 weeks. Then monthly for 3 months. DON or designee will audit all residents who require turning and positioning as part of wound treatment and CNA documentation will be reviewed for completeness weekly for 4 weeks. Then Monthly for 3 months. DON or designee will randomly audit 5 residents for heel bootie placement per plan of care weekly for 4 weeks. Then monthly for 3 months. All results will be brought to the QAPI committee monthly for a minimum of 3 months but will continue until the satisfaction of the QAPI committee is achieved. Responsible Party: Director of Nursing |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure cooking facilities were maintained in accordance with National Fire Protection Association 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations for 1 of 1 main kitchen fire suppression systems. Specifically, the monthly visual inspection for the main kitchen fire suppression system was not completed from (MONTH) 2024 to (MONTH) 2024. Findings include: The main kitchen fire suppression system's inspection tag was not completed from (MONTH) 2024 to (MONTH) 2024. The facility could not provide documentation that the monthly inspections had been completed. During an observation on 9/24/2024 at 11:35 AM, the main kitchen fire suppression system inspection tag had not been filled out from (MONTH) 2024 to (MONTH) 2024. During an interview on 9/25/2024 at 4:30 PM, the Maintenance Director stated they were not aware they had to inspect and document the kitchen fire suppression system monthly, they were not sure how to inspect the kitchen fire suppression system and had not been inspecting that monthly. The Maintenance Director stated it was important the kitchen fire suppression system functioned properly for the safety of residents and staff. 2012 NFPA 101 19.3.2.5.1, 9.2.3 2011 NFPA 96 11.2 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 The main kitchen fire suppression system was immediately inspected. All areas within the kitchen have the ability to be affected. Administrator educated Maintenance Director and Food Service Director on the importance of all fire suppression systems being up to date. Tags will be filled out monthly and suppression system will be checked monthly. The Administrator will audit the logs monthly for 3 months. Results will be brought to QAPI monthly for review. Responsible Party: Administrator |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure all emergency exit exterior discharge paths were maintained free of impediments with a level hard-packed all-weather travel surface to the public way for 1 isolated emergency exit (main kitchen external pathway). Specifically, the main kitchen external pathway had a ten-foot section that consisted of uneven broken brick. Findings include: During an observation on 9/24/2024 at 10:55 AM, the main kitchen external emergency pathway had a ten-foot section that consisted of uneven broken brick. This section was not a level hard-packed all-weather travel surface. During an interview on 9/25/2024 at 4:17 PM, the Maintenance Director stated they were aware that the main kitchen external emergency pathway was required to be level, but they were not aware of the ten-foot section of path identified during survey that was uneven and broken up. They stated they had seen this section of pathway before and did not realize it wasn't code compliant. The Maintenance Director stated it was important to ensure all external pathways were safe for residents and staff. 2012 NFPA 101 19.2.7, 7.1.6.3, 7.1.6.4, 7.1.10.1 CMS Survey and Certification Letter 05-38 10 NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 The ten foot section of path at end of main kitchen emergency pathway was corrected so as to provide a level hard-packed all-weather travel surface to the public way. Those exiting through the main kitchen external pathway have the ability to be affected. Administrator provided education to Maintenance Director on the importance of maintaining code compliant emergency pathways. Maintenance Director will visually audit the pathway monthly for 3 months. Results will be brought to QAPI Committee and any issues will be resolved immediately. Responsible Party: Maintenance Director |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure four of ten isolated egress exit doors functioned properly (exterior emergency exit double doors near resident room [ROOM NUMBER], exterior emergency exit double doors near resident room [ROOM NUMBER], emergency exit double doors near resident room [ROOM NUMBER], and exterior emergency exit single door in the main kitchen). Specifically, the above-mentioned exterior emergency exit doors did not self-close and latch when tested and the exit by room [ROOM NUMBER] required an excessive amount of force to open the door. Findings include: The facility's Exterior Doors Inspection form documented that the facility exterior emergency exit doors were inspected weekly between 7/1/2024 and 9/20/2024 by the Maintenance Director. The form documented that the doors were checked for function, closure operation, and positive latching. During an observation on 9/24/2024 at 9:45 AM, one of the exterior emergency exit double doors near resident room [ROOM NUMBER] did not self-close and latch when tested . Also, the door required a significant amout of force after three attempts did not freely open the door. During an observation on 9/24/2024 at 10:12 AM, one of the exterior emergency exit double doors near resident room [ROOM NUMBER] did not self-close and latch when tested . During an observation on 9/24/2024 at 10:50 AM, one of the exterior emergency exit double doors near resident room [ROOM NUMBER] did not self-close and latch when tested . During an observation on 9/24/2024 at 2:15 PM, the exterior emergency exit single door in the main kitchen did not self-close and latch when tested . During an interview on 9/25/2024 at 5:00 PM, the Maintenance Director verified that the exterior emergency exit doors were checked and documented weekly, and that they had initialed the forms when they completed the inspections. They were not aware that the doors identified during survey did not self-close and latch when tested . The Maintenance Director was not aware that one of the exterior emergency exit double doors near resident room [ROOM NUMBER] required more effort to open and stated that it was not like that last week. They stated it was important that all emergency exit doors functioned properly so residents and staff could evacuate when needed during an emergency event, and so residents could not elope from the facility. 2012 NFPA 101: 19.2.2.2.7 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved November 7, 2024 Exterior Emergency Door near room# 228 was adjusted and tested so it could be opened easily. Exterior Emergency Door near room# 120 was repaired so as to self-close and latch. Exterior Emergency Door near room# 111 was repaired so as to self-close and latch. Exterior Emergency Door in main kitchen was repaired so as to self-close and latch. All residents have the ability to be affected. Administrator educated and trained all maintenance staff and department heads on the importance of maintaining emergency exit doors and procedure. Maintenance Director or designee will audit emergency exit doors weekly to test the self-closing and latching. It will be audited weekly for 4 weeks and then monthly for 2 additional months. Results will be brought to QAPI on a monthly basis. Responsible Party: Maintenance Director/Administrator |
Scope: Widespread
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure electrical equipment was maintained in accordance with National Fire Protection Association 99 for 3 of 3 patient care related electrical equipment reviewed (activities room popcorn maker, resident room [ROOM NUMBER] electrical bed, South Unit floor scale), and for 3 of 3 non-patient care related electrical equipment reviewed (resident room [ROOM NUMBER] radio, compact disc player, and electric recliner). Specifically, the activities room popcorn maker lacked an electrical inspection sticker to document when it had entered the facility and a tracking identification number, resident room [ROOM NUMBER] electrical bed was not inspected annually, the South Unit floor scale was not electrically inspected in 2024; and the resident room [ROOM NUMBER] radio and compact disc player had not been electrically inspected in 2024, and the resident room [ROOM NUMBER] electric recliner lacked an electrical inspection sticker to document when it had entered the facility. Findings include: The facility's Electrical Equipment policy, last revised 5/2019, documented: - they would inspect and maintain all resident medical equipment as per user manufacturer guidelines. Equipment was to be tested before being put into service for the first time. Also, testing could not exceed 12 months. - At least annually or sooner if recommended by the manufacturer, all resident equipment would be inspected for safety. - All equipment would be tagged at the time of inspection. 1. Patient Care Related Electrical Equipment A. Popcorn Maker During an observation on 9/24/2024 at 2:50 PM, the activities room had a popcorn maker that lacked an electrical inspection label and a tracking identification number. During an interview on 9/26/2024 at 3:30 PM and 4:30 PM, the Maintenance Director stated the popcorn machine had been in the facility less than a year and it had been electrical inspected. They stated this piece of equipment did not have a tracking identification number, and they could not find any documentation to verify that the popcorn machine had been electrically inspected. B. Electric Bed The resident room [ROOM NUMBER]A electrical bed user manual documented the bed was required to be electrically inspected every 6 months. An undated Bed Audit form documented that the bed in resident room [ROOM NUMBER]A had the tracking identification number 0504- - -25. The Annual Electrical Testing of Beds, dated 2/9/2023, documented the bed in resident room [ROOM NUMBER]A was electrically safe but did not document the specific tracking identification number. During an observation and interview on 9/26/2024 between 3:30 PM and 4:30 PM, the resident room [ROOM NUMBER]A electrical bed had the tracking identification number 0504- - -16. The Maintenance Director stated since they were hired in (MONTH) 2023, they had not been told to electrically inspect electrical beds annually and was not given the bed inspection forms that had been used by the previous Maintenance Director. They stated there was no way to track the resident room [ROOM NUMBER]A electrical bed because beds were moved freely. The Maintenance Director was not aware that the facility's electrical beds were last annually inspected on 2/9/2023 and verified that the 2/9/2023 Annual Electrical Testing of Beds form did not include the tracking identification number. They stated they were not aware that as per the user manual this bed type was required to be electrically inspected every 6 months. C. Floor Scale The Annual Digital Wheelchair Scale Electrical PM form documented that the South Unit floor scale with the tracking identification number 7C 5 had been electrically inspected on 6/7/2023. During an observation and interview on 9/26/2024 between 3:30 PM and 4:30 PM, the south unit floor scale had the tracking identification number 7C 5. The Maintenance Director verified that the south unit floor scale had an electrical inspection label dated 3/13/2023 and was electrically inspected on 6/7/2023 as per the Annual Digital Wheelchair Scale Electrical PM form. They were not aware that this scale had not been electrically inspected in 2024, and there was no documentation to verify that this item had been electrically tested in 2024. 2.Non-Patient Care Related Electrical Equipment During an observation and interview on 9/26/2024 between 3:30 PM and 4:30 PM, resident room [ROOM NUMBER] had a radio with an electrical inspection label dated 4/2023, a compact disc player with an electrical inspection label dated 4/2023, and an electric recliner that lacked electrical inspection labels. The Maintenance Director stated they would electrically check resident owned equipment when the equipment entered the facility. They were not aware they had to do annual electrical checks on resident owned equipment. They stated the electric recliner in resident room [ROOM NUMBER] arrived about a year and a half ago and this piece of equipment had been electrically inspected, but they could not find any documentation to verify that the electric recliner had ever been electrically inspected. 2012 NFPA 99: 10.5.3 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 Popcorn maker in activities room, South Unit Floor Scale, Resident room# 203 compact disc player, radio, and electric recliner were inspected and an inspection label was put on each item. Tracking identification number has been added to the PCREE Inspection form. All other areas of the facility were inspected for similar issues and corrected if necessary. Administrator provided education to Maintenance Director, maintenance staff, therapy, activities, and front desk receptionists about the importance of all PCREE and non-PCREE devices being tested , inspected and labeled in accordance with NFPA 101. Administrator will audit 4 random PCREE and 4 random non-PCREE items and compare with binders weekly for 4 weeks and then monthly for 2 additional months. Results will be brought to QAPI Committee and any issues will be resolved. Responsible Party: Administrator/ Maintenance Director |
Scope: Widespread
Severity: Potential to cause more than minimal harm
Citation date: December 19, 2024
Corrected date: December 23, 2024
Citation Details Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that 2 of 2 natural gas emergency generators were properly maintained in accordance with National Fire Protection Association (NFPA) 99 (exterior 35-kilowatt natural gas generator, interior 35-kilowatt natural gas generator). Specifically, the exterior 35-kilowatt natural gas generator was located in an area that was not safe from vehicular traffic; the electrical room had miscellaneous storage that blocked access to the electrical panels; the transfer time from main power to the generators transfer switches and the actual times or hours the monthly load tests had been completed were not documented for both generators; and the three-year four-hour run test had not been completed for both generators. Findings include: 1. Generator Not Protected During an observation on 9/24/2024 at 10:55 AM, an external natural gas generator was not protected from vehicular traffic. The generator sat upon a concrete pad just off the parking lot by the dumpsters. The concrete was about 1 to 3-inches elevated from the parking lot from the front to the back of the concrete pad. During an interview on 9/26/2024 at 1:52 PM, the Maintenance Director verified that an external natural gas generator was located on a three-inch thick concrete pad and that the parking lot had a downward slope in the direction of the generator. They stated the concrete pad would not stop a vehicle from hitting the external generator. The Maintenance Director stated it was important that the generator was in a secure area so it could properly function and not get damaged. 2. Storage in Electrical Room During an observation on 9/24/2024 at 11:20 AM, the electrical room had the following items stored within 36-inches of the electrical panels: a broken electric wheelchair, a shop vacuum, a large bag of empty cans, an empty mop bucket, a large fan, numerous carts, and other miscellaneous items. During an interview on 9/26/2024 at 10:50 AM, the Maintenance Director stated the storage items located within the electrical room had been there prior to (MONTH) 2023. They were aware the electrical panels in the room had to have 36-inches of clearance for access and stated they had not thought about that requirement regarding the items stored in this room. 3. Missing Documentation on Generator Testing Form The monthly Generator Test - Full Load form, from 9/18/2023 to 9/2/2024, did not document the transfer time from the main power to the generators transfer switches, and the actual times or hours the monthly load tests had been completed. The comments section on this form documented a checkmark indicated the generator passed inspection. The full load must transfer in less than 10 seconds, and the generator sets were exercised monthly under load for 30 minutes. During an interview on 9/26/2024 at 2:05 PM, the Maintenance Director was not aware that the transfer time from main power to generator transfer switches was required to be documented. They stated the monthly Generator Test - Full Load form had been given to them by the current Administrator when they had taken over as the Maintenance Director in (MONTH) 2023, and this form did not include a spot to document the power transfer time, and actual times or hours the generator monthly load tests had been completed. They stated they had not seen the previous generator testing form that was completed by the previous Maintenance Director prior to (MONTH) 2023. That form did have boxes to document the transfer times of the generators and the actual times the monthly load tests had been completed and would have kept them in compliance. 4. Three-Year Four-Hour Run Test Not Completed The monthly Generator Test - Full Load form, from 9/18/2023 to 9/2/2024, had a comments section that documented the generators were to be exercised once every 36 months for 4 continuous hours. The facility could not provide documentation that a three-year four-hour run test had been completed in the last three years. During an interview on 9/26/2024 at 2:10 PM, the Maintenance Director was not aware that a three-year four-hour run test was required for both facility emergency generators, and this test had not been completed since they were hired in (MONTH) 2023. They stated they could not provide any documentation that a three-year four-hour run test had been completed within the last three years. The Maintenance Director stated it was important all testing for the generators was completed to ensure the generator would run during an emergency for the safety of residents and staff. 2012 NFPA 101: 9.1.3.1, 19.5.1 2011 NFPA 70: 110.26 (A)(1), 110.26 (E)(2) 2012 NFPA 99: 6.5.3.1 2010 NFPA 110: 8.4.9 10NYCRR 415.29(a)(2), 711.2(a)(1)Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that 2 of 2 natural gas emergency generators were properly maintained in accordance with National Fire Protection Association (NFPA) 99 (exterior 35-kilowatt natural gas generator, interior 35-kilowatt natural gas generator). Specifically, the three-year four-hour run test had not been completed for both generators. Findings include: Three-Year Four-Hour Run Test Not Completed The monthly Generator Test - Full Load form, from 9/18/2023 to 9/2/2024, had a comments section that documented the generators were to be exercised once every 36 months for 4 continuous hours. The facility could not provide documentation that a three-year four-hour run test had been completed in the last three years. During an interview on 9/26/2024 at 2:10 PM, the Maintenance Director was not aware that a three-year four-hour run test was required for both facility emergency generators, and this test had not been completed since they were hired in (MONTH) 2023. They stated they could not provide any documentation that a three-year four-hour run test had been completed within the last three years. The Maintenance Director stated it was important all testing for the generators was completed to ensure the generator would run during an emergency for the safety of residents and staff. During an interview on 12/4/2024 at 2:30PM, the Administrator stated they had completed the 3-year 4-hour load testing but had to locate the paperwork. Between 12/4/2024 and 12/16/2024 the Administrator provided multiple versions of the 3-year 4-hour load test that was completed on 10/3/2024 by the Maintenance Director. All documentation provided was for the generator in the generator room. No documentation was provided for the generator located outside of the facility. During an interview on 12/19/2024 at 4:53 PM, the Maintenance Director stated they had completed the generator load test on 10/3/2024 for the inside generator and 10/4/2024 for the outside generator. They stated the two generators were identical 30-kilowatt natural gas generators, but they were not sure if they ran together, or alternating to power the facility red outlets, lights, heating, air conditioning, and the walk-in coolers. They stated they calculated the load on the generators during the test and they were not sure why it wasn't documented on the original form but found the information on sticky notes, so they were able to add that when the form was updated. They did not know where the documentation was for the outside generator. During an interview on 12/19/2024 at 5:10 PM, the Administrator stated they were not sure where the documentation was for the outside generator and had thought that was provided, they did not realize they had only sent the documentation for the inside generator. 2012 NFPA 101: 9.1.3.1, 19.5.1 2011 NFPA 70: 110.26 (A)(1), 110.26 (E)(2) 2012 NFPA 99: 6.5.3.1 2010 NFPA 110: 8.4.9 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved December 27, 2024 Barriers installed to protect the natural gas generator outside the facility. All items in the electrical room have been removed. Generator testing times will be recorded going forward. All residents and staff have the potential to be affected however none were found to be affected. Administrator provided education to Maintenance Director on the importance of monthly generator tests and the correct documentation that should accompany it. Administrator provided education to Maintenance Director on the importance of keeping the electrical room clear. Administrator will audit generator test binder and will audit the electrical room to ensure it is kept free of obstructions weekly for 4 weeks and then monthly for 2 additional monthly. Results will be brought to QAPI and any issues will be resolved. Responsible Party: Administrator/ Maintenance Director |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on observation and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that the emergency lighting was tested and maintained for 1 of 1 emergency lights (generator room). Specifically, the annual 90-minute run test for the battery-operated emergency light in the generator room had not been completed in 2023, and the monthly 30-second run test was not documented from (MONTH) 2023 to (MONTH) 2024. Findings include: The facility could not provide documentation that the battery-operated emergency light in the generator room had an annual 90-minute run test in 2023 and the monthly 30-second run tests were completed from (MONTH) 2023 to (MONTH) 2024. During an observation on 9/26/2024 at 12:08 PM, the generator room contained a battery-operated emergency light. During an interview on 9/26/2024 at 12:10 PM, the Maintenance Director stated they were not aware of the battery-operated lighting monthly 30-second test and annual 90-minutes test requirements because they were not told about them when they took over as director in (MONTH) 2023. The Maintenance Director stated it was important that there was a backup light within the generator room during an emergency event or if generator repairs had to be made. 2012 NFPA 101: 19.2.9.1, 7.9 10NYCRR 415.29(a)(1&2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 Battery operated emergency light in generator room was tested for both a 90-minute annual run test and a 30-second monthly run test. Both results passed and were documented. The facility has the potential to be affected if the generator room does not have any lighting in the case of an emergency. Administrator provided education to Maintenance Director and maintenance staff on the importance of properly testing and maintaining battery-operated emergency lighting in the generator room. 30-second battery run tests will be conducted monthly. Annual 90-minute run tests will be conducted annually. The Administrator will audit the test logs monthly for 3 months. Results will be brought to QAPI Committee monthly for review. Responsible Party: Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on record review and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure the fire alarm system was maintained in accordance with the requirements of National Fire Protection Association 72 for 1 of 1 building fire alarm systems. Specifically, the fire alarm system semi-annual visual inspections were not completed in 2023. Findings include: The facility could not provide documentation that the fire alarm system semi-annual visual inspections were completed in 2023. During an interview on 9/26/2024 at 10:00 AM, the Maintenance Director stated they were not aware of the semi-annual visual inspection requirement for the facility's fire alarm initiating devices and had not been told of this requirement when hired as the Maintenance Director in (MONTH) 2023. They stated they could not provide any visual inspections of the fire alarm system for 2023. The Maintenance Director stated it was important that all fire alarm devices were inspected properly for the safety of residents and staff. 2012 NFPA 101: 19.3.4.1, 9.6.1.5 2010 NFPA 72: 14.1 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 The fire alarm system cannot be checked retroactively but will be visually checked semi-annually going forward. All residents in the building have the potential to be affected. Administrator educated Maintenance Director on the importance of visual checking the fire alarm system semi-annually to make sure it is in working condition. The Administrator will review the logs monthly for 3 months to ensure the facility is in compliance. Finding will be brought to QAPI committee. Responsible Party: Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on observation and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure fire drills were completed as required for 3 of 3 shifts (day shift, evening shift, night shift). Specifically, fire drills were not done at varying times for day shift and evening shift; and no fire drills were completed from (MONTH) 2023 to (MONTH) 2023. Findings include: 1. Missing Fire Drills The facility could not provide documentation that fire drills for the day shift, the evening shift, and the night shift had been completed from (MONTH) 2023 to (MONTH) 2023 (second and third quarter of 2023). During an interview on 9/25/2024 at 3:55 PM, the Maintenance Director stated they could not find any fire drills from (MONTH) 2023 to (MONTH) 2023. They stated it was important that all fire drills were completed so staff would know what to do if an actual fire occurred at the facility for the safety of residents and staff. 2. Fire Drills Not Completed at Varying Times The facility Fire Drill Reports documented the day shift (7:00 AM-3:00 AM) drills were conducted on the following dates and times: - 10/23/2023 at 10:45 AM; - 1/29/2024 at 10:45 AM; - 4/25/2024 at 10:30 AM; and - 7/25/2024 at 10:30 AM. The facility Fire Drill Reports documented the evening shift (3:00 PM-11:00 PM) drills were conducted on the following dates and times: - 11/28/2023 at 3:20 PM; - 2/27/2024 at 4:30 PM; - 5/22/2024 at 3:30 PM; and - 8/30/2024 at 4:35 PM. During an interview on 9/25/2024 at 3:55 PM, the Maintenance Director stated they had identified that fire drills had not been completed at varying times during a mock survey they completed last month. They stated that prior to this recent mock survey they were not aware that fire drills had to be completed at varying times for each shift. The Maintenance Director stated it was important to stagger fire drill times so staff would not know when a fire drill was going to be completed. 2012 NFPA 101: 19.7.1, 4.7 10NYCRR 415.29(a)(1&2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 Fire drills will be conducted at varying times for different shifts as required by regulations. All residents and staff have the potential to be affected. Administrator provided education to the Maintenance Director on the importance of conducting fire drills at varying times and staggering them for different shifts. Administrator will audit fire drill logs monthly for 3 months. Results will be brought to QAPI and any issues will be resolved. Responsible Party: Maintenance Director/ Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: December 19, 2024
Corrected date: December 30, 2024
Citation Details Based on observation and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that hazardous areas were maintained for 7 hazardous areas (clean side laundry room, dry food storage room, maintenance shop, electrical room, wheelchair storage room, break room/storage room, medical records storage room). Specifically, the doors to the clean side laundry room, the dry food storage room, the maintenance shop, the electrical room, and the wheelchair storage room were not self-closing and latching; the door frames for the clean side laundry room, the maintenance shop, the break room/storage room, the electrical room, and the wheelchair storage room were not fire-rated as required. Findings include: 1. Hazardous Area Doors Not self-closing and latching/doors in disrepair - During an observation on 9/24/2024 at 11:00 AM, the clean side laundry room door did not self-close and latch when tested . During an observation on 9/24/2024 at 11:04 AM, the dry food storage room door did not self-close and latch when tested . During an observation on 9/24/2024 at 11:09 AM, the maintenance shop door did not self-close and latch when tested . One door leaf was split and taped. During an observation on 9/24/2024 at 11:20 AM, the electrical room door did not self-close and latch when tested . The door scraped and caught on the floor, the door frame was bent and rusted, the door caught on the frame and remained ajar, and the door had modified hinges. During an observation on 9/24/2024 at 2:47 PM, the wheelchair storage room door did not self-close and latch when tested . During an interview on 9/26/2024 at 10:50 AM, the Maintenance Director stated the access door to the electrical room had been sticking to the floor if the door was fully opened and had not checked to see if the self-latch mechanism worked prior to survey. The Maintenance Director verified there had been modifications to the door and stated these had been installed prior to them taking over in (MONTH) 2023. During an interview on 9/26/2024 at 2:35 PM, the Maintenance Director was not aware that the access doors to the clean side laundry room, the dry food storage room, the maintenance shop, the electrical room, and the wheelchair storage room did not self-close and latch when tested . They stated they were aware of the requirements, these doors should have been self-closing and latching, and it was important that hazardous area doors were maintained for the safety of the residents and staff. 2. Hazardous Area Door Frames Not Rated During an observation on 9/24/2024 at 11:00 AM, the clean side laundry room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 11:09 AM, the maintenance shop door frame lacked a fire-rated label. Within the maintenance shop there was a metal fire cabinet that was in an open position and had been blocked from closing by dangling electrical cords stored on top of the cabinet. During an observation on 9/24/2024 at 11:18 AM, the break room/storage room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 11:20 AM, the electrical room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 2:47 PM, the wheelchair storage room door frame lacked a fire-rated label. During an interview on 9/26/2024 at 2:35 PM, the Maintenance Director stated they were not aware that the door frames for the clean side laundry room, the maintenance shop, the break room/storage room, and the wheelchair storage room were required to be fire-rated. The Maintenance Director stated they were not sure how long the maintenance shop flammable material metal cabinet had been kept in the open position and that this would increase the flammability of this room. They stated it was important that hazardous area door frames were maintained for the safety of the residents and staff. 2012 NFPA 101 19.3.2.1 10NYCRR 415.29(a)(2), 711.2(a)(1)Based on observation and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that hazardous areas were maintained for 7 hazardous areas (clean side laundry room, dry food storage room, maintenance shop, electrical room, wheelchair storage room, break room/storage room, medical records storage room). Specifically, the doors to the clean side laundry room, the dry food storage room, the maintenance shop, the electrical room, and the wheelchair storage room were not self-closing and latching; the door frames for the clean side laundry room, the maintenance shop, the break room/storage room, the electrical room, and the wheelchair storage room were not fire-rated as required. Findings include: 1. Hazardous Area Doors Not self-closing and latching/doors in disrepair - During an observation on 9/24/2024 at 11:00 AM, the clean side laundry room door did not self-close and latch when tested . During an observation on 9/24/2024 at 11:04 AM, the dry food storage room door did not self-close and latch when tested . During an observation on 9/24/2024 at 11:09 AM, the maintenance shop door did not self-close and latch when tested . One door leaf was split and taped. During an observation on 9/24/2024 at 11:20 AM, the electrical room door did not self-close and latch when tested . The door scraped and caught on the floor, the door frame was bent and rusted, the door caught on the frame and remained ajar, and the door had modified hinges. During an observation on 9/24/2024 at 2:47 PM, the wheelchair storage room door did not self-close and latch when tested . During an interview on 9/26/2024 at 10:50 AM, the Maintenance Director stated the access door to the electrical room had been sticking to the floor if the door was fully opened and had not checked to see if the self-latch mechanism worked prior to survey. The Maintenance Director verified there had been modifications to the door and stated these had been installed prior to them taking over in (MONTH) 2023. During an interview on 9/26/2024 at 2:35 PM, the Maintenance Director was not aware that the access doors to the clean side laundry room, the dry food storage room, the maintenance shop, the electrical room, and the wheelchair storage room did not self-close and latch when tested . They stated they were aware of the requirements, these doors should have been self-closing and latching, and it was important that hazardous area doors were maintained for the safety of the residents and staff. 2. Hazardous Area Door Frames Not Rated During an observation on 9/24/2024 at 11:00 AM, the clean side laundry room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 11:09 AM, the maintenance shop door frame lacked a fire-rated label. Within the maintenance shop there was a metal fire cabinet that was in an open position and had been blocked from closing by dangling electrical cords stored on top of the cabinet. During an observation on 9/24/2024 at 11:18 AM, the break room/storage room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 11:20 AM, the electrical room door frame lacked a fire-rated label. During an observation on 9/24/2024 at 2:47 PM, the wheelchair storage room door frame lacked a fire-rated label. During an interview on 9/26/2024 at 2:35 PM, the Maintenance Director stated they were not aware that the door frames for the clean side laundry room, the maintenance shop, the break room/storage room, and the wheelchair storage room were required to be fire-rated. The Maintenance Director stated they were not sure how long the maintenance shop flammable material metal cabinet had been kept in the open position and that this would increase the flammability of this room. They stated it was important that hazardous area door frames were maintained for the safety of the residents and staff. During an interview on 12/4/2024 at 2:30PM, the Administrator stated they were still pursuing the waiver to complete the work for K321. They had a vendor lined up to come out and evaluate the hazardous doors but needed to make some repairs prior to their visit. At that time the vendor would assess the doors and certify all that they could, any others would be replaced. 2012 NFPA 101 19.3.2.1 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved December 27, 2024 K-321 Request for Waiver Time Limitations and Need for Additional Time Doors that are immediately visible as beyond repair have been ordered through BR (NAME)son Doors. BR(NAME)son indicated that the door has been has been ordered and is expected to be received on (MONTH) 17th. Glass will then be installed on the doors and a subsequent installation will be scheduled. The BR(NAME)son is expecting to install the doors the first week of (MONTH) 2025. A Survey Work Order agreement has also been signed with Intertek who will be evaluating, certifying and labeling the facility fire doors and frames after the initial install of the ordered doors from BR(NAME)son. Intertek has indicated that some doors may pass and others may need to be replaced after evaluation if they still do not meet the requirements. This process may take additional time to complete as it may involve ordering, shipping, receiving and installing additional doors. Intertek may then be called back on-site to re-evaluate the additional work for certification and labeling. We anticipate this process should take no longer than 6 months to complete. We are anticipating a completion date no later than (MONTH) 26, 2025. Interim Measures 1. Facility has fire extinguishers throughout the building. The facility will add 6 additional Fire Extinguishers in the facility. 1 in each of the 2 Hallways, 2 in the Main Corridor and 2 in the Resident Dining Area. 2. The facility is fully sprinklered, utilizes a monitored full fire panel system and smoke detectors throughout the building. 3. The facility will conduct 2 Fire Drills per month so that staff may show competency with Fire Safety Procedures. 4. Additionally the facility will provide Monthly Emergency Procedure Training, specifically staff education about how to evacuate residents from the facility in a safe and expedient manner in the event of smoke and/or fire. Quarterly Updates We will be submitting, at a minimum, quarterly progress reports to LTCLSCwaivers@health.ny.gov based on the date approved. P(NAME) 1. a. The clean side laundry room door was repaired so as to self-close and latch. b. The dry food storage room door was repaired so as to self-close and latch. c. The maintenance shop door was repaired so as to self-close and latch. d. The wheelchair storage room door was repaired so as to self-close and latch. e. Electrical room door was repaired so as to self-close and latch. f. The clean side laundry room door and frame will be evaluated and certified by vendor or replaced as needed. g. The maintenance shop door and frame will be evaluated and certified by vendor or replaced as needed. h. All dangling electrical cords were immediately removed. i. The break room door and frame will be evaluated and certified by vendor or replaced as needed. j. The electrical room door and frame will be evaluated and certified by vendor or replaced as needed. k. The wheelchair storage door and frame will be evaluated and certified by vendor or replaced as needed. 2. The doors and doorframes to these hazardous areas have to be maintained for the safety of the residents and staff. 3. Administrator gave education to Maintenance Director and maintenance staff on the importance of maintaining safe hazardous areas. This includes the self-closing and latching of fire rated doors and frames. 4. The Administrator will audit the test logs monthly for 3 months. Results will be brought to QAPI monthly for review. Responsible Party: Administrator |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on observation and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that the corridors were maintained for 1 isolated area (basement corridor) reviewed. Specifically, the basement corridor egress pathway was obstructed. Findings include: During an observation on 9/24/2024 at 11:15 AM, the basement corridor had multiple items (broken lifts, racks with resident clothing, housekeeping carts, linen carts, spare wheelchairs, empty dietary plastic racks an industrial fan, garbage cans, boxes of residents' belongings, etc.) stored along both sides of the corridor. There was a pallet at the end of the hall that blocked access to one of the emergency exit doors. This corridor egress pathway was not free of obstructions and approximately less than two-feet wide due to the items stored within the hallway. During an interview on 9/25/2024 at 4:10 PM, the Maintenance Director stated supply pallets would be brought into the basement corridor by the vendor and dropped in the front of the emergency exit doors. They stated that with the other items stored on both sides of this corridor and the pallet, that the egress pathway was blocked. The Maintenance Director was aware that items should only be stored on one side of the hallway, and stated there was no other place to store some of the items such as the boxes of residents' belongings and the broken lifts. They stated it was important for all corridors to be cleared in case of an emergency. 2012 NFPA 101 19.2.1 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved November 7, 2024 Basement corridor was cleared of obstructions in egress pathway. Anyone leaving by basement corridor egress has the ability to be affected. Administrator educated all staff on the importance of keeping the basement corridor clear of obstructions in egress pathway. Additional storage spaces will be utilized to ensure that the basement corridor remains free of obstructions. Administrator will audit the basement location with a visual check to ensure that the egress is not blocked. It will be audited weekly for 4 weeks and then monthly 2 additional months. Results will be brought to QAPI on a monthly basis. Responsible Party: Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on record review and interview conducted during the Emergency Preparedness Plan (EP) review in conjunction with a Life Safety Code Survey completed on 9/24/2024 to 9/26/2024, the facility did not ensure their shelter in place procedure policy contained all relevant information. Specifically, the shelter in place procedure policy lacked the main location and alternate location for the sheltering of residents, and staff. Findings include: The facility's Emergency Procedure - Shelter in Place policy, last reviewed 3/2018, had incomplete documentation for the following areas within the facility that were identified as suitable spaces that were structurally sound and away from potential exposure areas for residents, staff, and visitors to seek shelter in the following locations: - main location __________; and - alternate location __________. During an interview on 9/25/2024 at 5:48 PM, the Administrator verified that their shelter in place policy had incomplete documentation for the main shelter location and the alternate shelter location. They stated this policy was a universal policy given to the facility by the corporate office and that the fillable sections had not been filled in with specific facility information. The Administrator stated it was important that information was included in the facility emergency preparedness plan and they should have been documented properly. 42 CFR 483.73(b)(4) | Plan of Correction: Approved October 23, 2024 The Emergency Preparedness Plan and the shelter in place procedure policy was updated to reflect main location and alternate location for the sheltering of residents, and staff. All residents have the potential to be affected however none were found to have been affected. Facility Emergency Preparedness Plan and Shelter in place policy does not need any additional revisions. Regional Director provided Education to Administrator on importance of having properly filled out Shelter in place procedures and policies. Administrator will audit the policy for any updates weekly for 4 weeks and then monthly 2 additional months. Results will be brought to QAPI on a monthly basis. Responsible Party: Administrator / Regional Administrator |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure that fire extinguishers were maintained in accordance with National Fire Protection Association 10 Standard for Portable Fire Extinguishers for 2 isolated fire extinguishers (maintenance shop, main kitchen). Specifically, a fire extinguisher in the maintenance shop had not been inspected monthly as required, and the main kitchen had a fire extinguisher that the gauge showed the extinguisher required recharging. Findings include: The facility's Fire Extinguishers Monthly Check sheet, from 7/2/2024 to 9/2/2024, documented that the facility fire extinguishers located in the maintenance shop and kitchen had been inspected by the Maintenance Director and passed inspection. During an observation on 9/24/2024 at 11:07 AM, the maintenance shop had an ABC-type fire extinguisher that was last inspected on 1/3/2024. This extinguisher was mounted to the wall under a fire extinguisher sign. There were three additional extinguishers on the floor beneath this extinguisher, each with an appropriately dated and inspected tag. During an observation on 9/24/2024 at 12:49 PM, the main kitchen had a K-type fire extinguisher that the gauge showed the extinguisher required recharging. During an interview on 9/24/2024 at 2:15 PM, the Maintenance Director was not aware that the main kitchen K-type fire extinguisher was not charged and stated they had not seen that during the previous month's inspection. They stated fire extinguisher monthly visual checks included making sure the extinguishers were secured and charged. During an interview on 9/25/2024 at 4:52 PM, the Maintenance Director was not aware of the ABC-type fire extinguisher that had last been visually inspected on 1/3/2024. They verified that this extinguisher was properly secured to the wall and under a fire extinguisher sign. The Maintenance Director stated it was important all fire extinguishers were visually checked monthly for the safety of residents and staff. 2012 NFPA 101 19.3.5.12, 9.7.4.1 2010 NFPA 10 10 NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 Fire extinguisher, ABC type in maintenance shop was immediately inspected and initialed. K-type extinguisher in main kitchen was replaced. Other areas of the facility were reviewed for similar issues but none were found. Administrator provided education to the Maintenance Director and maintenance staff on the importance on checking and making sure the fire extinguishers inspected monthly. Administrator or designee will conduct a random audit of 6 fire extinguishers weekly for 4 weeks then monthly for 2 additional months. Results will be brought to QAPI committee and any issues will be resolved. Responsible Party: Maintenance Director/ Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details Based on record review and interview conducted during the Emergency Preparedness Plan (EP) review in conjunction with a Life Safety Code Survey completed on 9/24/2024 to 9/26/2024, the facility did not ensure their tracking system policy contained all relevant information. Specifically, the tracking system policy lacked the location of the handheld scanner, where the wrist bands were located, and where the paper barcodes log was located. Findings include: The facility policy E-finds last revised 2/2020, had sections that were not completed. The policy documented the following: - Handheld scanner issued be NYSDOH, located __________; - Other scanners identified as compatible __________; - The Facility has wrist bands equal to the number .These are located __________. - Paper Barcodes Log that includes a list of all assigned barcodes .patient data (name, DOB, gender, etc.) located __________; and - Facility staff names assigned to eFINDS Administrator and eFINDS Data Reporter rolls can be found in the __________. During an interview on 9/25/2024 at 5:40 PM, the Administrator verified that the policy had multiple blank sections that had not been filled out by the facility. They stated this policy was a universal policy given to the facility by the corporate office and that the fillable sections had not been filled in with specific facility information. The Administrator stated it was important that the locations of the emergency tracking equipment and forms were documented in the facility emergency preparedness plan, and they should have been documented properly. 42 CFR 483.73(b)(2) | Plan of Correction: Approved October 23, 2024 The E-finds policy was updated to reflect the location of the handheld scanner, wrist bands and paper barcodes. All residents have the potential to be affected if the E-finds would need to be used however none were found to be affected. Facility E-finds policy last revised 2/2020 does not need any additional revisions. Regional Director provided Education to Administrator on importance of having properly filled out E-find policies. E-finds scanner and wristbands and paper barcodes can be located in Administrators office. Administrator will audit the location and E-finds policy weekly for 4 weeks and then monthly for 2 additional months. Results will be brought to QAPI on a monthly basis. Responsible Party: Administrator / Regional Administrator |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 22, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure the building was properly maintained and protected throughout by an approved automatic sprinkler system for 3 isolated areas (electrical room, nursing office/Director of Nursing office smoke compartment, linen room near resident room [ROOM NUMBER]). Specifically, the electrical room lacked sprinkler coverage, the nursing office/DON office smoke compartment contained both quick response sprinkler heads and standard response sprinkler heads, and a sprinkler head in the linen room near resident room [ROOM NUMBER] was installed too close to an overhead light. Findings include: The facility's sprinkler inspection report dated 8/19/2024, did not document any sprinkler installation deficiencies. 1. Missing Sprinkler Coverage During an observation on 9/24/2024 at 11:20 AM, the electrical room lacked sprinkler coverage. The room was used as a storage room for numerous carts, bags of garbage and recycling, and other miscellaneous combustible items. The room also contained a smaller closet area that contained combustible storage items. The closet area lacked electrical panels. During an interview on 9/26/2024 at 10:50 AM, the Maintenance Director stated they knew the electrical room was not sprinklered because there was electrical equipment located in that room. They stated the storage items located within this room had been there prior to (MONTH) 2023 and that due to this room being used for storage it should have been sprinklered. 2. Mixed Sprinkler Heads During an observation on 9/24/2024 at 1:34 PM, the nursing office had two quick response sprinkler heads and the Director of Nursing office had two standard response sprinkler heads. The two offices were both part of the same smoke compartment and separated by a door that lacked a self-closure device. During an interview on 9/26/2024 at 10:22 AM, the Maintenance Director stated they were not aware that the nursing and the Director of Nursing office were within one smoke compartment which had both quick response sprinkler heads and standard response sprinkler heads. They were not aware that this was not allowed. The Maintenance Director stated they relied upon their vendor to keep them code compliant. They stated they were not aware of how to identify sprinkler types and ratings prior to guidance provided during survey. The Maintenance Director stated it was important that proper sprinkler heads were installed in the facility for the safety of residents and staff. 3. Sprinkler Head Installation During an observation on 9/24/2024 at 2:49 PM, the linen room near resident room [ROOM NUMBER] had a sprinkler head that had been installed that was touching the overhead light. During an interview on 9/26/2024 at 10:30 AM, the Maintenance Director stated they were aware that sprinklers had to be installed far enough away from an obstruction so a sprinkler head could function properly. They stated that during rounding of the facility they had identified a sprinkler head in the linen room near resident room [ROOM NUMBER] touching the overhead light but they were focused on the 18-inch clearance underneath the sprinkler head and did not do anything about the clearance beside the sprinkler. The Maintenance Director stated it was important for the sprinklers to properly function for the safety of residents and staff. NFPA 101: 19.3.5.1, 9.7.1.1 2010 NFPA 13 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved November 7, 2024 The storage items found in the electrical room were removed so as to remove the need for sprinkler coverage. Sprinkler head in DON Office were replaced so as to be compliant with NFPA 101. Overhead light in linen closet near room# 220 relocated so as not to obstruct sprinkler head. Other areas of the facility were reviewed for similar issues but none were found. Administrator educated all staff regarding the importance of fire sprinklers throughout the facility to ensure the safety of the residents and staff. Administrator will provide random audits of 6 sprinkler heads weekly for 4 weeks then monthly for 2 additional months. Results will be brought to QAPI Committee and any issues will be addressed. Responsible Party: Administrator/Maintenance Director |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: December 16, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation, and interview during the Life Safety Code recertification survey conducted [DATE]-[DATE], the facility did not ensure 1 of 1 automatic sprinkler systems were maintained for 10 rooms (activities storage closet, hall outside the conference room, main kitchen, janitors closet, North Unit hall closet, basement stairwell, maintenance shop, hall outside the nursing office, South Unit hall, and generator room). Specifically, there were missing escutcheons in the activities storage closet, the hall outside the conference room, and the North Unit hall closet; there were missing ceiling tiles in the main kitchen and the janitor's closet; a missing spare sprinkler; expired sprinklers in the hall outside the nursing office and the South Unit hall; and the dry sprinkler heads in the generator room, walk-in freezer, and the walk-in cooler ages were unknown. Findings include: The facility's sprinkler inspection report dated [DATE] documented the following: - all extra heads were in the spare head cabinet. - the quick response sprinkler heads were dated 1990, heads had been sent out for testing on [DATE], all were tested normal, and sprinkler heads were good until 2028; and - new dry sidewall sprinkler heads were dated (YEAR). 1. Missing ceiling tiles and escutcheons: During an observation on [DATE] at 9:50 AM, the activities storage closet had a sprinkler head without the escutcheon. During an observation on [DATE] at 12:51 PM, the hall outside the conference room had a sprinkler head without the escutcheon. During an observation on [DATE] at 2:20 PM, the main kitchen ceiling near the three bay sink had two missing ceiling tiles. During an observation on [DATE] at 2:20 PM, the janitor's closet had 1 missing two-foot by three-foot ceiling tile, and 2 other tiles that were dangling down and not properly aligned. During an observation on [DATE] at 2:40 PM, the North Unit hall closet had a sprinkler head without the escutcheon. During an interview on [DATE] at 11:15 AM, the Maintenance Director stated they were not aware that there were sprinkler heads with missing escutcheons in the activities storage closet, the hall outside the conference room, and the North Unit hall closet. They stated they would have expected the sprinkler vendor to identify missing escutcheons during the quarterly sprinkler inspections, and they had not typically looked at the sprinkler heads during their rounding of the facility. The Maintenance Director was not aware of the missing ceiling tiles in the main kitchen and the condition of the ceiling in the janitor's closet. They stated it was important that escutcheons and ceiling tiles were in place to prevent smoke and heat from entering above the ceiling tiles and bypassing the sprinklers. 2. Missing Spare Sprinkler Head During an observation on [DATE] at 10:46 AM, the basement stairwell had a red quick response vertical sprinkler head. During an observation on [DATE] at 11:07 AM, the maintenance shop spare sprinkler head boxes did not contain a red quick response vertical sprinkler head. During an interview on [DATE] at 11:00 AM, the Maintenance Director was aware the facility was required to have spares for each type of sprinkler located in the facility. They were not aware that the sprinkler vendor quarterly inspection reports checked yes on all quarterly sprinkler inspections from (MONTH) 2023 to (MONTH) 2024 regarding the spare sprinklers. 3. Outdated Sprinkler Heads During an observation on [DATE] at 1:37 PM, the hall outside the nursing office, and the entire South Unit hall had quick response sprinkler heads dated 1990. Quick response sprinkler heads were required to be tested or replaced after [AGE] years, and then again ten years after that. During an interview on [DATE] at 10:05 AM, the Maintenance Director was aware that the quick response sprinkler heads in the hall outside the nursing office, and the entire South Unit hall were dated 1990. The Maintenance Director stated they were not aware that the [DATE] quarterly sprinkler inspection report documented that sprinkler heads had been tested in (YEAR). They stated they did not have any documentation that showed the (YEAR) sprinkler testing had been completed. 4. Unknown age of Sprinkler Heads During an observation and interview on [DATE] at 10:58 AM, the generator room off the back of the building had two side wall sprinkler heads. The Maintenance Director stated they believed the sprinklers were dry heads. They and the surveyor could not find the dates of these sprinkler heads. During an observation on [DATE] at 11:35 AM, and again on [DATE] at 5:15 PM, the age of the dry sprinkler heads in the main kitchen walk-in freezer and walk-in cooler could not be determined. During an interview on [DATE] at 5:15 PM, the Maintenance Director verified and stated they could not find the dates on the dry sprinkler heads located in the generator room, the walk-in cooler, and the walk-in freezer. They were aware that dry heads were required to be replaced every ten years, and stated they could not verify the age of these sprinkler heads or when they were installed. The Maintenance Director stated it was important that all sprinklers were maintained for the safety of the residents and staff. 2012 NFPA 101: 19.3.5.1, 9.7.5 2011 NFPA 25 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved December 5, 2024 **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Escutcheons were added to the activitys storage closet, the hall outside the conference room, and the North Unit Hall closet. Ceiling tiles were replaced in the main kitchen ceiling near the three bay sink. Ceiling tiles were replaced in the janitors closet. Expired sprinklers in the hall outside the nursing office and the South Unit Hall were tested by the vendor in (YEAR). Dry sprinkler heads in the walk-in freezer, and the walk-in cooler were replaced in (YEAR). Paperwork/Invoice from vendor was found. Dry sprinkler heads for generator room will be evaluated on [DATE] and replaced within the week if needed. Other areas of the facility were reviewed for similar issues but none were found. Administrator provided education to Maintenance Director on ensuring that fire sprinkler heads are in compliance with NFPA 101. Administrator or designee will conduct a random audit of 6 escutcheons and 6 ceiling tiles weekly for 4 weeks then monthly for 2 additional months. Findings will be brought to QAPI and any concerns will be addressed then. Responsible Party: Administrator/ Maintenance Director |
Scope: Pattern
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: November 29, 2024
Citation Details Based on record review, observation, and interview during the Life Safety Code recertification survey conducted 9/24/2024-9/26/2024, the facility did not ensure smoke barrier doors were properly maintained for 2 of 4 smoke barriers (smoke barrier near resident room 102, smoke barrier near resident room 202). Specifically, the above-mentioned smoke barriers had unsealed penetrations. Findings include: During an observation on 9/26/2024 at 4:55 PM, the smoke barrier near resident room 202 had an unsealed hole with a data wire that passed through the wall. During an observation on 9/26/2024 at 5:00 PM, the smoke barrier near resident room 102 had an unsealed hole with multiple data wires that passed through the wall. During an interview on 9/26/2024 at 5:05 PM, the Maintenance Director stated the facility smoke barriers were inspected by the previous Maintenance Director after the last federal survey in 2023 and had assumed that any unsealed penetrations had been sealed. They stated that since being hired as Maintenance Director in (MONTH) 2023 they had not checked the smoke barriers. The Maintenance Director stated the unsealed penetration located in the smoke barrier near resident room 202 was part of a data wire project that was completed approximately six months ago. 2012 NFPA 101 19.3.7.3 10NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved October 23, 2024 Unsealed hole near resident room 102 and 202 were repaired. Other areas of the facility were reviewed for similar issues but none were found. Administrator provided education to Maintenance Director and maintenance staff in regards to making ensuring smoke barriers are properly sealed. Administrator or designee will conduct a random audit of 6 smoke barrier areas for penetrations weekly for 4 weeks then monthly for 2 additional months. Results will be brought to QAPI Committee and any issues will be resolved. Responsible Party: Maintenance Director/ Administrator |
Scope: Isolated
Severity: Potential to cause more than minimal harm
Citation date: September 26, 2024
Corrected date: December 10, 2024
Citation Details **NOTE- TERMS IN BRACKETS HAVE BEEN EDITED TO PROTECT CONFIDENTIALITY** Based on record review, observation and interview during the Life Safety Code recertification conducted 9/24/2024-9/26/2024, the facility did not ensure smoke barrier doors were properly maintained for 1of 4 smoke barriers (smoke barrier near resident room [ROOM NUMBER]). Specifically, one of the two doors for the smoke barrier near resident room [ROOM NUMBER] was in disrepair and the double doors for the same smoke barrier did not properly close. Findings include: During an observation on 9/24/2024 at 10:05 AM, one of two smoke barrier doors near resident room [ROOM NUMBER] was damaged. The door was spit with the which exposed the interior material of the door. The door had a previous repair that consisted of three screws to keep the door from delaminating. Also, the damaged door did not close flush with the other door when tested . During an interview on 9/25/2024 at 4:40 PM, the Maintenance Director stated they were aware that one of the two doors for the smoke barrier near resident room [ROOM NUMBER] was damaged, had the inner door material exposed, and the door was modified with screws through the door that held it together. They were aware that the double doors for the smoke barrier near resident room [ROOM NUMBER] did not close flush as designed and stated that if the doors did not close properly smoke could pass through them. The Maintenance Director stated the facility smoke barriers were inspected annually but this was not documented. They stated it was important that all smoke doors worked as designed and were properly maintained for the safety of residents and staff. 2012 NFPA 101: 19.3.7.6 10 NYCRR 415.29(a)(2), 711.2(a)(1) | Plan of Correction: Approved December 3, 2024 K-374 Request for Waiver Time Limitations and Need for Additional Time Smoke barrier door near room# 122 was ordered through BR (NAME)son Doors. The vendor indicated that the door has been has been ordered and is expected to be received on (MONTH) 17th. Glass will then be installed on the doors and a subsequent installation will be scheduled. The vendor is expecting to install the doors the first week of (MONTH) 2025. We are requesting an additional 60 days to cover any shipping, weather-related or otherwise unforeseen circumstances. We are anticipating a completion date no later than (MONTH) 26, 2025. Interim Measures 1. Facility has fire extinguishers throughout the building. The facility will add 6 additional Fire Extinguishers in the facility. 1 in each of the 2 Hallways, 2 in the Main Corridor and 2 in the Resident Dining Area. 2. The facility is fully sprinklered, utilizes a monitored full fire panel system and smoke detectors throughout the building. 3. The facility will conduct 2 Fire Drills per month so that staff may show competency with Fire Safety Procedures. 4. Additionally the facility will provide Monthly Emergency Procedure Training, specifically staff education about how to evacuate residents from the facility in a safe and expedient manner in the event of smoke and/or fire. Quarterly Updates We will be submitting, at a minimum, quarterly progress reports to LTCLSCwaivers@health.ny.gov based on the date approved. P(NAME) 1. Smoke barrier door near room# 122 will be replaced. 2. All residents have the potential to be affected if a smoke barrier door is not working properly. 3. Administrator provided education to the Maintenance Director and maintenance staff on the importance of smoke barrier doors being in compliance. 4. Administrator will audits 4 smoke barrier doors weekly for 4 weeks and then monthly for 2 additional monthly. Results will be brought to QAPI and any issues will be resolved. Responsible Party: Administrator/Maintenance Director |